Instructions for installation and servicing ecoTEC

6.2 

Handing over to the user

•  Set the maximum radiator temperature control to the 

desired setting.

•  Set the maximum hot water temperature control to 

the desired setting.

•  Instruct the user in the safe and efficient operation of 

the boiler, in particular the function of
–  the boiler on/off control
–  the maximum radiator temperature control
–  the maximum hot water temperature control (only 

800 and pro series)

–  the pressure gauge

•  Show the user how to operate any external controls.
•  Explain to the user the importance of having the boiler 

regularly serviced by a competent servicing company.
To ensure regular servicing, it is strongly recommend-
ed that arrangements are made for a Maintenance 
Agreement. Please contact Vaillant Service Solutions 
(0870 6060 777) for further details.

•  Record central heating operating pressure in the 

Benchmark Log Book along with the heat input (kW) 
and temperature difference between flow and return.
Failure to install and commission this appliance in 
compliance with the manufacturers instructions may 
invalidate the warranty (Note: This does not affect 
your statutory rights).

•  Leave the user instructions, installation instructions 

and log book with the user.

Inspection and maintenance

7.1 Initial 

inspection

To ensure the continued safe and efficient operation of 
the boiler it is recommended that it is checked and serv-
iced as necessary at regular intervals. The frequency of 
servicing will depend upon the particular installation 
conditions and usage, but in general once per year 
should be adequate.

  Danger!

It is law that all servicing work is carried out by 
a competent person (CORGI registered).
Inspections/Maintenance work not carried out 
by a competent person can result in damage to 
property and personal injury.

Only genuine Vaillant spare parts may be used for 
inspections, maintenance and repair work to ensure the 
long-term working order of all functions of your Vaillant 
appliance.
Any spare parts which might be required are contained 
in the current spare parts catalogues.
Information can be obtained from Vaillant Customer 
Service Centres.

7.1.2 Safety 

instructions

Important:
Before starting any maintenance work:

•  Isolate the mains electricity supply by disconnecting 

the plug at the socket outlet (if there is only an isolat-
ing switch remove the fuse from the switch).

•  Turn OFF the gas supply at the gas service valve fitted 

to the boiler.

•  When removing any water carrying components 

ensure that water is kept away from all electrical com-
ponents.

•  Always use new seals and O–rings when parts are 

replaced.

•  Always test for gas soundness and always carry out 

functional checks after any service work and after 
replacing any gas carrying component.

•  Always check earth continuity, polarity and resistance 

to earth with a multimeter after any service work and 
after replacing any electrical component.

  Danger!

Electrocution by touching live parts can be 
fatal!
The supply terminals in the appliance switch 
box are live even if the main ON/OFF switch is 
turned off.
Protect the switch box from spray water.
Before working on the appliance, turn off the 
power supply and secure against restart!

Always perform the following steps after completing any 
inspection tasks:
•  Open the maintenance taps in the heating supply and 

return and in the cold water inlet (only 800 series).

•  If necessary, refill the device with hot water up to a 

pressure of approx 1.5 bar and evacuate the heating 
system.

•  Open the maintenance tap in the gas supply pipe.
•  Turn on the power supply and the main switch.
•  Check the appliance for gas and water leaks.
•  Fill and evacuate the heating system again, if neces-

sary.

  Note

If it is necessary to keep the main switch on for 
certain inspection and maintenance, this is indi-
cated in the description of the maintenance 
task.

  Note

The boiler is fitted with a combustion analysis 
test point. A suitable combustion analyser can 
be connected to this point to establish the com-
bustion performance of the boiler. It is not nec-
essary to check the CO

2

 content or adjust the 

air ratio of the boiler during the annual service. 
Checking/adjustment of this value is only 
required in the following instances; replacement 
of gas valve, conversion to or from Natural Gas/ 
LPG or if incorrect combustion is suspected 
(see Section 9.7).

6 Commissioning Part II
7 Inspection and maintenance

Содержание ecoTEC pro 28

Страница 1: ...plus 612 ecoTEC plus 615 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 824 ecoTEC plus 831 ecoTEC pro 28 Instructions for installation and servicing ecoTEC Wall hung room sealed fan assi...

Страница 2: ...13 Electrical connection 22 4 13 1 General requirements 22 4 13 2 Connection to the main supply 23 4 13 3 Electric board layout 24 4 13 4 Connection of programmable thermostats 27 4 14 Controls ecoTEC...

Страница 3: ...e condensation water siphon 42 7 4 Checking the expansion vessel 43 7 5 Recommissioning the boiler 43 7 6 Test operation 43 8 Troubleshooting 44 8 1 Logical fault finding procedure 44 8 1 1 Status cod...

Страница 4: ...coTEC 800 range consists of 2 models with out puts of 23kW and 31kW for domestic hot water and a pro version with an output of 28kW for domestic hot water All versions are available in natural gas The...

Страница 5: ...the adherence to the inspec tion and maintenance conditions Danger Any incorrect use is forbidden The appliances must be installed by a qualified engineer who is responsible for adhering to the exist...

Страница 6: ...rature at minimum thermal load 40 C flow 30 C return at maximum thermal load 80 C flow 60 C return 40 70 C C NOx class 5 Protection class IP X4D max flow temperature 85 C Adjustable flow temperature D...

Страница 7: ...ad 80 C flow 60 C return 1 9 5 5 1 9 6 9 2 8 8 3 4 1 11 1 4 7 13 8 g s g s Exhaust temperature at minimum thermal load 40 C flow 30 C return at maximum thermal load 80 C flow 60 C return 40 70 C C NOx...

Страница 8: ...nnection 15mm only 800 series 3 Gas connection 15mm 4 Hot water connection 15mm only 800 series 5 Heating flow pipe 22mm 6 Hanging bracket 7 Flue hole flue system 60 100 8 Flue hole flue system 80 125...

Страница 9: ...er valve with by pass 7 Pump 8 Aqua Sensor 9 Electronics box 10 Pressure sensor 11 Hot water heat exchanger 12 Gas valve 13 Heat exchanger 14 Flue pipe connection 1 2 3 4 5 7 9 14 13 12 10 Fig 2 3 Fun...

Страница 10: ...n BS 5449 Specification for forced circulation hot water for domestic premises BS 5546 Specification for gas hot water supplies for domestic premises BS 6700 Services supplying water for domestic use...

Страница 11: ...s extra 1 sticker each for tank and ventilation above Fig Table 3 1 Scope of delivery for ecoTEC plus 600 series 1 2 3 4 6 5 8 9 7 Fig 3 2 Scope of delivery for ecoTEC plus 800 series DO NOT remove th...

Страница 12: ...flat vertical wall which must be suffi ciently robust to take the weight of the boiler The boiler may be installed on a combustible wall subject to the requirements of the Local Authorities and Build...

Страница 13: ...nu ine Vaillant flue pipes Malfunctions can occur if you use other accessories These may result in damage and injury You will find a list of genuine flue pipes in the Vaillant installation manual for...

Страница 14: ...rminal on the same wall 300 M Distance from adjacent for vertical Flue 500 Table 3 4 Terminal position for a fan assisted concentric flue Note In addition the terminal should not be nearer than 150 mm...

Страница 15: ...ogies Tandem House Marlow Way Croydon CR0 4XS Tel 0870 8700362 3 10 2Filling and preparing heating system The system can be filled using the built in filling loop ecoTEC plus 800 series only or via a...

Страница 16: ...is fitted with an automatic air vent Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually 3 12 Conde...

Страница 17: ...and condensate drain 4 1 2 Unpack the boiler To unpack the boiler cut both plastic carton straps open box and lift out the polystyrene top packing Lift the cardboard box upwards Note Care should be ta...

Страница 18: ...Lift the boiler 3 up to the wall so that it is slightly above the hanging bracket 1 Note Lift the boiler from either side at the bottom edge Lower the boiler slowly onto the hanging bracket so that t...

Страница 19: ...Insert the union nut 2 and the pinching ring 3 on the gas connection pipe 1 to the heater Insert the union nut 6 and the pinching ring 5 on the conduit arc provided with ecoTEC plus appliances 7 Inser...

Страница 20: ...tra care should be taken to avoid damage to isolation valves through heat transfer 4 10 1 Heating flow and return connection Note Before connecting the heating circuit to the boiler all pipework and r...

Страница 21: ...10 2Pressure Relief Valve 1 2 3 Fig 4 11 Installing the drain pipe on the pressure release valve of the heating system picture shows ecoTEC 800 plus Caution To ensure fumes do not escape through the s...

Страница 22: ...ap with a 75mm 3 seal The connection should preferably be made down stream of the sink waste trap If the connection is only possible upstream then an air break is needed between the two traps This is...

Страница 23: ...the control panel Fig 4 13 Opening the electronics box Unclip the bottom of the terminal box cover and hinge back to reveal the connection plugs Feed the power supply flex into the appliance and the c...

Страница 24: ...24 Instructions for installation and servicing ecoTEC 4 13 3 Electric board layout Fig 4 15 Connection wiring ecoTEC 4 Boiler installation sequence...

Страница 25: ...black X 20 8 blue X 2 12 green X 2 11 red X 2 9 black Pump X 20 18 red 24 VDC X 20 9 blue earth X 20 16 blue earth X 20 13 black X 20 12 black X 20 4 grey PWM X 20 3 black Hall signal X 20 17 red 24...

Страница 26: ...nsor NTC return X 20 5 red X 20 7 black X 20 7 black X 20 8 blue X 2 10 black X 2 14 brown X 2 12 green X 2 11 red X 2 9 black Pump X 20 18 red 24 VDC X 20 9 blue earth X 20 16 blue earth X 20 13 blac...

Страница 27: ...ection details for programmable thermostats 4 14 Controls ecoTEC plus 800 and pro only 4 14 1 External electrical controls The boiler terminals 3 4 and 5 are for connecting exter nal electrical contro...

Страница 28: ...EP 4002 EP 5002 Smiths Timeguard SupplyMASTER FST11 FST17 Sunvic Select 107 N 1 A B C N 4 2 L L 3 3 4 1 2 6 5 E 4 L 3 N 3 E N E 2 3 4 N E 1 L L 3 5 6 4 L N 2 3 4 L N 3 4 1 L N 2 3 4 L N 3 4 1 L N 2 3...

Страница 29: ...or use in systems with thermostatic radiator valves no separate system by pass is required For opti mum fuel economy where TRV s are used they must be used in conjunction with a boiler control interlo...

Страница 30: ...thermostat 2 1 C YL 3 3 2 2 BK 1 2 2 1 1 RED C 1 1 3 ACL Drayton HTS3 Danfoss Randall ATC Tower CS1 Honeywell L641 Horstmann HTC1 Siemens Landis Staefa RAM 1 Sunvic SA 2452 8 4 7 E Cylinder thermosta...

Страница 31: ...all ATC Tower CS1 Honeywell L641 Horstmann HTC1 Siemens Landis Staefa RAM 1 Sunvic SA 2452 10 7 E Cylinder thermostat 3 E 2 E E EARTH BLUE BROWN GREY ORANGE Central heating 2 port motorised valve 4 E...

Страница 32: ...ing the heating system 5 4 1 Checking the filling pressure of the heating system bar i F P plus pro bar 1 2 Fig 5 1 Checking the filling pressure of the heating system Note The ecoTEC appliances come...

Страница 33: ...filling pipe of the heating system Open the cold water dispensing valve Slowly open the filling valve and let the water flow into the heating system Ventilate the lowest heating ele ment until the wa...

Страница 34: ...of the condensate water siphon 5 7 Adjusting the pumping capacity Only in ecoTEC plus The capacity of the two stage pump can be adjusted to the requirements of the heating system If needed change the...

Страница 35: ...ve U gauge Tighten the test point screw and check for leaks Record appliance working gas inlet pressure mbar in the Benchmark Installation Commissioning and Service Log Book 5 9 3 Checking the gas rat...

Страница 36: ...ltaneously to cancel adjustment mode Adjustment mode is also cancelled if no button is operated for a period of 4 minutes Appliance Heating output in kW ecoTEC plus 612 5 12 ecoTEC plus 615 5 15 ecoTE...

Страница 37: ...ating system and the heater quickly and fully Close the drain valve Fill the heating system again with water as described in Section 5 4 4 Release water from the system until the system design pressur...

Страница 38: ...be obtained from Vaillant Customer Service Centres 7 1 2 Safety instructions Important Before starting any maintenance work Isolate the mains electricity supply by disconnecting the plug at the socket...

Страница 39: ...nts if necessary X X 7 Check re pressurise expansion vessel as necessary X 8 Open the maintenance taps fill up the appliance system up to approx 1 0 2 0 bar depending on the static height of the syste...

Страница 40: ...kwards to remove from the appliance Turn off the gas service valve Turn off the boiler CH service valves Loosen screw release the front case spring retaining clips located beneath the front edge of th...

Страница 41: ...components Any water used to clean the main heat exchanger will drain through the condensate trap Avoid pointing the water jet directly at the insulating surface 2 on the back of the heat exchanger I...

Страница 42: ...line to hold the gas fittings Turn on the gas supply and test for soundness Refit the air inlet pipe ensuring that the blue seal in the air intake pipe is correctly located 7 3 Cleaning the condensati...

Страница 43: ...heating system 7 5 Recommissioning the boiler Carry out electrical safety checks Turn on the electrical supply Open the boiler CH service valves Carry out function checks of boiler operation as previ...

Страница 44: ...y shows the status code e g S 04 for Burner mode Heating The display of the status codes can be cancelled as fol lows Press the i key or Do not press any key for about 4 minutes The current heating fl...

Страница 45: ...alue by holding down the i key for approx 5 seconds until the display no longer flashes You can end the diagnosis mode as follows Press the i and keys simultaneously or Do not press any key for approx...

Страница 46: ...number 00 to 99 d 90 Digital regulator status 1 identified 0 unidentified eBUS Address 10 d 91 DCF status with connected external probe with DCF77 receiver 0 no reception 1 reception 2 synchronised 3...

Страница 47: ...ting max output d 78 Storage charging temperature limit target flow tem perature in storage mode Adjustment range in C 55 to 90 Factory setting 80 d 80 Heating operating hours in h d 81 Water heating...

Страница 48: ...ion plug defective ionisation current stopped cable electrode faulty earthing in appliance electronics defective F 29 Flame goes off during operation and subsequent ignition attempts failed Gas supply...

Страница 49: ...all adjustable diagnosis points now correspond to the factory settings 9 Parts replacement The tasks listed below in this section may be carried out only by a qualified engineer Only use genuine spar...

Страница 50: ...ull out the plug 3 from the fan Remove the three screws 2 on the compact thermo module 1 Remove the complete gas valve fan unit 5 Fig 9 3 Gas fitting fan screwed joint Remove both fixing screws 5 on t...

Страница 51: ...he work check for water leaks and perform a function check see Section 7 6 9 5 Replacing primary heat exchanger Danger Before replacing the component comply with the safety instructions in Section 9 1...

Страница 52: ...g electronics and display Danger Before replacing the component comply with the safety instructions in Section 9 1 Comply with the assembly and installation manuals provided with the spare parts Repla...

Страница 53: ...le 9 2 by turning the screw 2 Turn to the left higher CO2 content Turn to the right lower CO2 content Note Only for natural gas Adjust only in increments of 1 8 turn and wait approx 1 minute after eac...

Страница 54: ...rgely 92 of metal components designed for eventual recycling by incorpo ration into the smelting process of a steelworks This gives these parts virtually unlimited scope for subse quent re use All pla...

Страница 55: ......

Страница 56: ...839592_00 GB 11 2004...

Отзывы: