Inspection and maintenance
Instructions for installation and servicing ecoTEC 839592_13
53
7
Settings
Natural gas (H)
Tolerance
Propane
Tolerance
Unit
CO
2
after 5 min. full load
mode with appliance front
closed
9.2 1,0
10.2 0,5
Vol.–%
CO
2
after 5 min. full load
mode with appliance front
removed
9.0 1,0
10.0 0,5
Vol.–%
Set for Wobbe-Index W
0
15
22.5
kWh/m
3
CO value with full load
< 250
< 250
ppm
CO/CO
2
< 0,0031
< 0,0026
Table 7.1 Factory gas setting
a
Danger!
Risk to life due to poisoning!
CO is an extremely toxic gas. Risk to life due
to excessive CO concentrations.
>
If you are not able to adjust the boiler cor-
rectly and the flue gas values remain
higher than allowed in Table 7.1, call the
Vaillant Service Solutions.
>
Do not start up the boiler.