5
Installation Manual auroMATIC 560 0020060907_00
GB
a
Caution!
An optional electric heating element (EP) must
be fitted with an additional relay or contactor
with a circuit-breaking capacity of at least 16 A.
Never connect an electric heating element to
the auroMATIC 560 without an additional ex-
ternal relay or contactor.
Caution!
The C1/C2 contact is a 24 V low-voltage con-
tact and may not under any circumstances be
used as a 230 V switching contact.
5.1
Wiring as per the hydraulic plan
To simplify installation there are three hydraulic plans
stored in the controller, from which the one most appro-
priate to the system configuration must be selected.
The hydraulic plans each show a possible system config-
uration in which some system components are optional.
a
Caution!
These hydraulic plans are only schematic repre-
sentations and cannot be used for the prepara-
tion of the hydraulic piping.
Hydraulic
plan
Bivalent cylin-
der
Monovalent cyl-
inder
Number of col-
lectors
Circulation
pump incorpo-
rated
Solid fuel boiler
incorporated
2nd cylinder
or swimming pool
incorporated
1
X
1
Yes
No
Yes
X
1
No
No
Yes
2
X
2
No
No
Yes
3
X
1
No
Yes
Yes
Table 5.1 System configuration