70
Installation and maintenance instructions 0020297933_07
5.12
Connecting the condensate discharge pipe
Danger!
Risk of injury due to frozen condensate.
Frozen condensate on paths may cause falls.
▶
Ensure that condensate does not dis-
charge onto paths and that ice cannot
build up there.
1.
For all installation types, ensure that any condensate
that accumulates is discharged frost-free.
1
2
3
4
Validity:
Floor installation
Condition
: Version without drain pipework
▶
Install the supplied condensate discharge tundish
(3)
.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and into the downpipe.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
▶
Ensure that the condensate discharge tundish is posi-
tioned in the centre above the downpipe in the gravel
bed.
Condition
: Version with drain pipework
▶
Install this design only in regions without ground frost.
▶
Install the supplied condensate discharge tundish
(3)
and adapter
(2)
.
▶
Connect the drain pipework to the adapter.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and the adapter and into
the drain pipework.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
Validity:
Wall-mounting
Condition
: Version without drain pipework
▶
Install the supplied condensate discharge tundish
(3)
.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and to the outside.
▶
Slide the end of the heating wire from the outside
through the condensate discharge tundish and back
to the inside until it forms a U-shape within the con-
densate discharge tundish.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
▶
Use the gravel bed below the product to drain away
the condensate.
Condition
: Version with drain pipework
▶
Install the supplied condensate discharge tundish
(3)
and adapter
(2)
.
▶
Connect the drain pipework to the adapter and to a
downpipe. In doing so, ensure that there is a sufficient
downward gradient.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and the adapter and into
the drain pipework.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
▶
If the region is one with ground frost, install electrical
trace heating for the drain pipework.
Validity:
Flat roof installation
Condition
: Version without drain pipework
▶
Install the supplied condensate discharge tundish
(3)
.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and to the outside.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
▶
Use the flat roof to drain away the condensate.
Condition
: Version with drain pipework
▶
Install the supplied condensate discharge tundish
(3)
and adapter
(2)
.
▶
Connect the drain pipework to the adapter and to a
downpipe over a short distance. In doing so, ensure
that there is a sufficient downward gradient.
▶
Slide the heating wire
(1)
from inside through the con-
densate discharge tundish and the adapter and into
the drain pipework.
▶
Adjust the internal heating wire in such a way that the
loop
(4)
lies concentric to the hole in the floor plate.
▶
If the region is one with ground frost, install electrical
trace heating for the drain pipework.