Installation and maintenance instructions 0020297933_07
4.1.2
Protective zone for ground installation in
front of a building wall
C
D
A
B
A
2100 mm
B
3100 mm
C
200 mm/250 mm
D
1000 mm
Dimension C is the minimum clearance that must be main-
tained to the wall (
4.1.3
Protective zone for ground installation in a
building corner
A
B
C
D
E
F
G
A
2100 mm
B
2600 mm
C
200 mm/250 mm
D
500 mm
E
1000 mm
F
500 mm
G
1800 mm
The right-hand corner of the building is shown here. Dimen-
sions C and D are the minimum clearances that must be
maintained to the wall (
Section 5.4). Dimension D varies
for the left-hand corner of the building.
4.1.4
Protective zone for wall installation in front
of a building wall
C
D
A
B
A
2100 mm
B
3100 mm
C
200 mm/250 mm
D
1000 mm
The protective zone below the product extends as far as the
floor.
Dimension C is the minimum clearance that must be main-
tained to the wall (