Set-up 4
0020258610_00 ecoVIT exclusiv Installation and maintenance instructions
9
4.5
Minimum clearances
B
B
A
C
Minimum clearance
A
500 mm
B
At least 500 m, only required on one side
C
300 mm for the pipe group and condensate
pump accessories, 400 mm for the cylinder
charging connection set accessory in the case
of a flush combination with an
actoSTOR
4.6
Clearance from combustible components
It is not necessary to maintain a clearance between the
product and components made of combustible materials that
goes beyond the minimum clearances (
→
Page 8).
Note
However, you must ensure that there is sufficient
clearance behind and beside the product in order
to position the condensate discharge pipe safely
above a drain or, if required, to connect a con-
densate pump. The drain must be visible.
4.7
Aligning the product
▶
Use the height-adjustable feet to adjust the product ho-
rizontally in order to ensure that the condensate drains
from the flue gas collector.
4.8
Opening the front flap
▶
Take hold of the recessed handle in the front flap and lift
the panel up slightly.
◁
The front flap automatically swivels downwards and
the control panel becomes accessible.
4.9
Hinging the electronics box down and up
4.9.1
Hinging down the electronics box
1
2
1.
Turn both screws
(1)
by 90°.
2.
Hinge the electronics box
(2)
down.
4.9.2
Hinging up the electronics box
1.
Hinge the electronics box
(2)
up.
2.
Turn both screws
(1)
by 90°.
4.10
Removing and installing the upper casing
4.10.1 Removing the upper casing
1.
Open the front flap. (
→
Page 9)
2.
Hinge the electronics box down. (
→
Page 9)
1
2
3.
Reach through behind the panel
(2)
from below and
push the upper casing
(1)
upwards.
4.
Remove the upper casing.