20 • vacon
lonworks interface
Tel: +358-201-2121 • Fax: +358-201-212 205
6
nviRstFault
This input network variable provides
a fault reset. Setting value 1 for State and a non-zero value for
Value will reset an active fault in Vacon NX. Default value is 0; 0.
State Value
Command
0
any
no action (0; 0)
1
0
no action (0; 1)
1
> 0
reset fault (200 ; 0)
-1 (0xFF)
any
invalid (no action)
Table 6-3.
nviClrCntr
This input network variable provides a mechanism to clear the kWh trip counter or the Drive total
running hours trip counter.
1
MWh trip counter
2
Operation day trip counter
nviProcessIn1..8
These input network variables are sent directly to the application (see more detailed explanation in
chapter 6.5 Process data)
The valid range is 0 to 65535 (-163,840 to 163,835).
nviDigitalIn1..8
These input network variables are sent directly to the application (see more detailed explanation in
chapter 6.5 Process data) Default value is 0; 0.
state value
command
0
any
off (0; 0)
1
0
off (0; 1)
1
> 0
on (200; 1)
-1 (0xFF)
any
invalid (no action)
Table 6-4.