26 • vacon
lonworks interface
Tel: +358-201-2121 • Fax: +358-201-212 205
6
nciMinOutTime
This configuration property defines the minimum period of automatic network variable tansmission.
nciNmlSpeed
This configuration property is used to provide the nominal speed of the motor in RPM. This value is
necessary to determine the minimum and maximum speeds for the motor, based on the configuration
properties nciMinSpeed, nciMaxSpeed (entered as a percentage of nominal speed).
nciNmlFreq
This configuration property is used to provide the nominal frequency for the motor.
nciRampUpTm
Defines the acceleration time for Vacon NX. The valid range is 0.0 to 6,553.4 sec (0.1 sec).
nciRampDownTm
Defines the deceleration time for Vacon NX. The valid range is 0.0 to 6,553.4 sec (0.1 sec).
nciDrvSpeedScale
This configuration property is used as the default value for
nviDrvSpeedScale
. This value will be
adopted at power-up and in case no input variable within the specified Receive Heartbeat time is
received.
Archived Document