22 • vacon
lonworks interface
Tel: +358-201-2121 • Fax: +358-201-212 205
6
If the read command is successful then nvoParOut value is
- LN_RECALL 112 <0 0 5 A0> 0 0 0 0
If the read command fails then nvoParOut value is
- LN_ LN_NUL 112 <0 0 0 0> 0 0 0 0
6.3
Output Network Variables
Function
Variable Name
SNVT type
Min.
Max. Value
Node Object status
nvoStatus
SNVT obj status
Drive speed feedback
nvoDrvSpeed SNVT lev percent
-163.840% +163.830%
Actual motor current
nvoDrvCurnt
SNVT amp
0.0A 3276.7A
Actual drive power nvoDrvPwr
SNVT power kilo
0,0 kW
6553,5 kW
Drive total running hours
nvoDrvRunHours
SNVT time hour
0 h
65535
Status word
nvoDrvStatus
SNVT state
n/a n/a
kWh trip counter
nvoDrvEnrgy
SNVT elect kwh
0kWh 65535kWh
Active fault code
nvoActFault
SNVT count
0
41
Process Out
nvoProcessOut1..8
SNVT lev percent
0 65535
Digital Out
nvoDigitalOut1..8
SNVT switch
0 4
Parameter Out
nvoParResp
SNVT preset
- -
Table 6-6. Network output variables
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive object.
Field Description
object_id
ID of object within node
invalid_id
1 means requested ID is not implemented
in this node
invalid_request
1 means request for unimplemented
function
disabled
1 means object disabled
electrical_fault
1 means drive is faultefd
in_alarm
1 means drive is in alarm
report_mask
1 means status is an event mask
Table 6-7.