5.3.2
CABLE AND FUSE SIZES FOR 500-690 V, FR6 TO FR9
Table 26: The cable and fuse sizes for Vacon
®
NXS and NXP
Frame
Type
I
L
[A]
Fuse
(gG/gL) [A]
Mains,
motor and
brake
resistor
cable Cu
1)
[mm
2
]
Terminal cable size
Mains cable
terminal
[mm
2
]
Grounding
terminal
[mm
2
]
FR6
0004 6—0007 6
3–7
10
3*2.5+2.5
2.5–50 Cu
6–50 Al
2.5–35
0010 6—0013 6
10–13
16
3*2.5+2.5
2.5–50 Cu
6–50 Al
2.5–35
0018 6
18
20
3*4+4
2.5–50 Cu
6–50 Al
2.5–35
0022 6
22
25
3*6+6
2.5–50 Cu
6–50 Al
2.5–35
0027 6—0034 6
27–34
35
3*10+10
2.5–50 Cu
6–50 Al
2.5–35
FR7
0041 6
41
50
3*10+10
2.5–50 Cu
6–50 Al
6–50
0052 6
52
63
3*16+16
2.5–50 Cu
6–50 Al
6–50
FR8
0062 6—0080 6
62–80
80
3*25+16
25–95 Cu/Al
6–95
0100 6
100
100
3*35+16
FR9
0125 6—0144 6
0170 6
125–144
170
160
200
3*95+50
95–185
Cu/Al2
6–95
0208 6
208
250
3*150+70
1)
uses a correction factor 0.7
POWER CABLING
VACON · 51
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]