NOTE!
For other possible installation combinations, speak to the distributor near you.
3.3
STORAGE
If you must keep the AC drive in storage before you use it, make sure that the ambient
conditions agree to these:
Storage temperature: –40…+70°C (-40...+158°F)
Relative humidity: 0 to 95%, no condensation
If you must keep the AC drive in storage for a long time, you must connect the power to the
AC drive each year. Keep the power on for a minimum of 2 hours.
We do not recommend a long storage time. If the storage time is more than 12 months, you
must charge the electrolytic DC capacitors with caution. To reform the capacitors, obey the
instructions in Chapter 8.6.1 Capacitor reforming.
3.4
REMOVING THE PACKAGING AND LIFTING THE AC DRIVE
To lift the AC drives larger than FR7 out of the package, use a jib crane. Speak to the factory
or the distributor near you to get information on how to lift the AC drive safely.
After you lift the drive, do a check for signs of damage on the drive.
3.4.1
WEIGHT OF THE AC DRIVE
The weights of AC drives of different frames are very different. It can be necessary for you to
use a lifting device to move the drive from its package.
Table 4: The weights of the different frames
Frame
Weight, IP21/IP54 [kg]
Weight, UL Type 1 / Type 12 [lb.]
FR4
5.0
11.0
FR5
8.1
17.9
FR6
18.5
40.8
FR7
35.0
77.2
FR8
58.0
128
FR9
146
322
FR10
340
750
FR11 *
470
1036
*) FR11, the product types 0460 and 0502: 400 kg (882 lb.)