CHANGING THE HMI ACKNOWLEDGEMENT TIME
1
In the Hardware settings submenu, find the HMI
acknowledgement time with the Browser buttons.
READY
I/O term
HMI ACK timeout
200ms
2
To go to the edit mode, push the Menu button Right.
READY
I/O term
HMI ACK timeout
200ms
3
To change the acknowledgement time, use the
Browser buttons.
4
To accept the change, push the Enter button.
7.9.7.4
Number of retries to receive HMI acknowledgement (P6.7.4)
Use this parameter to set the number of times the AC drive tries to receive
acknowledgement if it does not receive it during the acknowledgement time (P6.7.3) or if the
received acknowledgement is defective.
CHANGING THE NUMBER OF RETRIES TO RECEIVE HMI ACKNOWLEDGEMENT
1
In the Hardware settings submenu, find the
Number of retries to receive HMI
acknowledgement with the Browser buttons.
2
To go to the edit mode, push the Menu button Right.
The value starts to blink.
3
To change the number of retries, use the Browser
buttons.
4
To accept the change, push the Enter button.
7.9.7.5
Sine filter (P6.7.5)
When you use an old motor or a motor that was not made to be used with an AC drive, it may
be necessary to use a sine filter. A sine filter makes the sine form of the voltage better than a
du/dt filter.
If you have a sine filter in your AC drive, to put it into operation set this parameter to
Connected.
7.9.7.6
Pre-charge mode (P6.7.6)
If you have an FI9 or a larger inverter unit, select 'Ext.ChSwitch' to control an external charge
switch.