48 • vacon
cabling and connections
Tel: +358-201-2121
•
Fax: +358-201-212 205
6
5
Connect the cables:
Remove the screws of the cable protection plate. Do not open the
cover of the power unit!
Make holes into and pass the cables through the rubber
grommets on the bottom of the power unit. The rubber grommets
are delivered in a separate bag.
Connect the DC supply, motor and control cables into their
respective terminals.
For Information on cable installation according to UL
regulations, see Chapter 6.1.3.
Cable installation according to EMC regulations:
The output cables to the motor must be 360
o
EMC earthed. The
EMC grounding clamps can, for instance, be installed on the
mounting plate. The EMC grounding clamps must be suited to the
output cable diameter to give a 360
o
contact with the cables.
Make sure that the control cable wires do not come in contact with
the electronic components of the unit.
Check the connection of the earth cable to the motor and the
inverter terminals marked with
.
Connect the separate shield of the power cable to the earth
terminals of the inverter, motor and the supply centre.
Attach the cable protection plate with the screws.
Ensure that the control cables or the cables of the unit are not
trapped between the frame and the protection plate.