42 • vacon
cabling and connections
Tel: +358-201-2121
•
Fax: +358-201-212 205
6
NXI_1300 5
1300
170M8547
3SHT
690
1250
6
NXI_1450 5
1450
170M8547
3SHT
690
1250
6
NXI_1770 5
FI14
1770
170M8547
3SHT
690
1250
2 × 6
NXI_2150 5
2150
170M8547
3SHT
690
1250
2 × 6
NXI_2700 5
2700
170M8547
3SHT
690
1250
2 × 6
Table 6
-
2. Fuses used in Vacon NXI (465 - 800Vdc)
6.1.1.4
Fuses, NXI_xxxx 6
Type
Frame
IL
[A]
Bussman aR
fuse type
Fuse
size
Fuse
Un
[V]
Fuse
In
[A]
No. of fuses
NXI_0125 6
FI9
125
170M4199
1SHT
1250
400
2
NXI_0144 6
144
170M4199
3SHT
1250
400
2
NXI_0170 6
170
170M4199
3SHT
1250
400
2
NXI_0208 6
208
170M4199
3SHT
1250
400
2
NXI_0261 6
FI10
261
170M6305
3SHT
1250
700
2
NXI_0325 6
325
170M6305
3SHT
1250
700
2
NXI_0385 6
385
170M6277
3SHT
1250
1000
2
NXI_0416 6
416
170M6277
3SHT
1250
1000
4
NXI_0460 6
FI12
460
170M6305
3SHT
1250
700
4
NXI_0502 6
502
170M6305
3SHT
1250
700
4
NXI_0590 6
590
170M6305
3SHT
1250
700
4
NXI_0650 6
650
170M6277
3SHT
1250
1000
4
NXI_0750 6
750
170M6277
3SHT
1250
1000
4
NXI_0820 6
820
170M6277
3SHT
1250
1000
4
NXI_0920 6
FI13
920
170M6305
3SHT
1250
700
6
NXI_1030 6
1030
170M6277
3SHT
1250
1000
6
NXI_1180 6
1180
170M6277
3SHT
1250
1000
6
NXI_1500 6
FI14
1500
170M6277
3SHT
1250
1000
2 × 6
NXI_1900 6
1900
170M6277
3SHT
1250
1000
2 × 6
NXI_2250 6
2250
170M6277
3SHT
1250
1000
2 × 6
Table 6-3. Fuses used in Vacon NX (640 - 1100V)
Information about fuses:
gR fuses are designed to protect the device against both overcurrent and short-circuits.
aR fuses protect the cables of the device against short-circuits.
gG fuses are generally used to protect cables against overcurrent and short-circuits.
Содержание NXI
Страница 1: ...vacon nxi inverters fi9 fi14 user manual ...
Страница 24: ...24 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 2 Vacon NXI dimensions FI10 ...
Страница 26: ...26 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 4 Vacon NXI dimensions FI12 front view ...
Страница 104: ......