technical data
vacon • 17
24-hour support: +358-(0)40-
8371 150 • Email: [email protected]
4
4.2
Power ratings
4.2.1
Vacon NXI_xxxx 5 – Supply voltage 465-800 Vdc, Motor voltage 380—500 Vac
High overload =
Max current I
S
; 2 sec/20 sec, 150% overloadability; 1 min/10 min
Following continuous operation at rated output current, 150 % rated
output current (I
H
) for 1 min, followed by a period of load current less
than rated current, and of such duration that the r.m.s output current,
over the duty cycle, does not exceed rated output current (I
H
)
Low overload = Max current I
S;
, 2 sec/20 sec, 110% overloadability; 1 min/10 min
Following continuous operation at rated output current, 110% rated
output current (I
L
) for 1 min, followed by a period of load current less
than rated current, and of such duration that the r.m.s output current,
over the duty cycle, does not exceed rated output current (I
L
)
Table 4
-
1. Power ratings and dimensions of Vacon NXI, supply voltage 465—800Vdc
Note: The rated currents in given ambient temperatures are achieved only when the switching
frequency is equal to or less than the factory default.
Motor voltage 380-500 Vac, 50/60 Hz, 3~
Inverter type
Loadability
@ 40 °C ambient temperature
Motor shaft power
Frame
Dimensions and weight
W
×
H
×
D/kg
Low
High
513Vdc
supply
675Vdc
supply
Rated
continuous
current I
L
(A)
10%
overload
current
(A)
Rated
continuous
current
I
H
(A)
50%
overload
current
(A)
Max
current
I
S
10%
overload
40°C
P(kW)
50%
overload
40°C
P(kW)
10%
overload
40°C
P(kW)
50%
overload
40°C P(kW)
NXI_0168 5
170
187
140
210
238
90
75
110
90
FI9
239 × 1030 × 372/65
NXI_0205 5
205
226
170
255
285
110
90
132
110
FI9
239 × 1030 × 372/65
NXI_0261 5
261
287
205
308
349
132
110
160
132
FI9
239 × 1030 × 372/65
NXI_0300 5
300
330
245
368
444
160
132
200
160
FI9
239 × 1030 × 372/65
NXI_0385 5
385
424
300
450
540
200
160
250
200
FI10
239 × 1030 × 552/100
NXI_0460 5
460
506
385
578
693
250
200
315
250
FI10
239 × 1030 × 552/100
NXI_0520 5
520
572
460
690
828
250
250
355
315
FI10
239 × 1030 × 552/100
NXI_0590 5
590
649
520
780
936
315
250
400
355
FI12
2×239 × 1030 × 552/200
NXI_0650 5
650
715
590
885
1062
355
315
450
400
FI12
2×239 × 1030 × 552/200
NXI_0730 5
730
803
650
975
1170
400
355
500
450
FI12
2×239 × 1030 × 552/200
NXI_0820 5
820
902
730
1095
1314
450
400
560
500
FI12
2×239 × 1030 × 552/200
NXI_0920 5
920
1012
820
1230
1476
500
450
630
560
FI12
2×239 × 1030 × 552/200
NXI_1030 5
1030
1133
920
1380
1656
560
500
710
630
FI12
2×239 × 1030 × 552/200
NXI_1150 5
1150
1265
1030
1545
1854
630
560
800
710
FI13
708 × 1030 × 553/302
NXI_1300 5
1300
1430
1150
1725
2070
710
630
900
800
FI13
708 × 1030 × 553/302
NXI_1450 5
1450
1595
1300
1950
2340
800
710
1000
900
FI13
708 × 1030 × 553/302
NXI_1770 5
1770
1947
1600
2400
2880
1000
1200
FI14
2×708 × 1030 × 553/302
NXI_2150 5
2150
2365
1940
2910
3492
1200
1500
FI14
2×708 × 1030 × 553/302
NXI_2700 5
2700
2970
2300
3287
3933
1500
1800
FI14
2×708 × 1030 × 553/302
Содержание NXI
Страница 1: ...vacon nxi inverters fi9 fi14 user manual ...
Страница 24: ...24 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 2 Vacon NXI dimensions FI10 ...
Страница 26: ...26 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 4 Vacon NXI dimensions FI12 front view ...
Страница 104: ......