22 • vacon
commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
AV14
Temperature Rise
Calculated motor
temperature 100,0% =
nominal temperature of
motor
NOT IN NXL -series
Percent
R
AV15
FBProcessDataOut1
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV16
FBProcessDataOut2
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV17
FBProcessDataOut3
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV18
FBProcessDataOut4
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV19
FBProcessDataOut5
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV20
FBProcessDataOut6
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV21
FBProcessDataOut7
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV22
FBProcessDataOut8
Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV23
Active Fault Code
Active Fault Code
-
R
AV24
Speed Reference
Speed Reference,
percentage of nominal
speed
Percent
C
AV25
Current Limit
Current Limit
Amps
W
AV26
Min Frequency
Minimum Frequency
Hz
W
AV27
Maximum Frequency
Maximum Frequency
Hz
W
AV28
Accel Time
Acceleration Time
seconds
W
AV29
Decel Time
Deceleration Time
seconds
W
AV30
FBProcessDataIN 1
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV31
FBProcessDataIN 2
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV32
FBProcessDataIN 3
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV33
FBProcessDataIN 4
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV34
AnyParam ID
ID number that is used
in AV35
0.0 to 65535.0
resolution 1.0
W
AV35
AnyParam Value
Value of ID defined by
AV34
-32768.0 to +32767.0
resolution
W
AV36
FBFixedControlWord PDI 0
1) (see next page)
C
AV37
FBGeneralControlWord PDI 1
2) (see next page)
C
AV38
FBFixedStatusWord PDO 0
3) (see next page)
R
AV39
FBGeneralStatusWord PDO 1
4) (see next page)
R
NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.