background image

20 • vacon 

 

commissioning 

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205 

 

7.5.1

 

Binary Value Object 

 

Instance ID 

Object Name 

Description 

Inactive / Active 

Present Value  
Access Type 

BV0 

Ready State 

Indicates whether the 
drive is ready or not 

Not Ready / Ready 

BV1 

Run/Stop State 

Indicates whether the 
drive is running or 

stopped 

Stop / Run 

BV2 

Fwd/Rev State 

Indicates the rotation 
direction of the motor 

Fwd / Rev 

BV3 

Fault State 

Indicates if a fault is 
active 

OK / Fault 

BV4 

Warning State 

Indicates if a warning is 
active 

OK / Warning 

BV5 

At Setpoint 

Ref. Frequency reached 

False / True 

BV6 

At Zero Speed 

Motor Running at zero 
speed 

False / True 

BV7 

General 0 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV8 

General 1 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV9 

General 2 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV10 

General 3 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV11 

General 4 

Application specific bit 
from drives General 

Status Word 

0 / 1 

BV12 

General 5 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV13 

General 6 

Application specific bit 
from drives General 
Status Word 

0 / 1 

BV14 

General 7 

Application specific bit 
from drives General 

Status Word 

0 / 1 

BV15 

Run/Stop CMD 

Command to start drive 
(FB control is active) 

Stop / Run 

BV16 

Fwd/Rev CMD 

Command to change 
rotational direction (FB 
control is active) 

Fwd / Rev 

BV17 

Reset Fault 

Command to reset 
Active Fault from dirve 

0 / Reset 

BV18 

FBFixedControlWord 

Bit_3 

Application Specific bit 

From the Fixed Control 
Word 

0 / 1 

BV19 

FBFixedControlWord 
Bit_4 

Application Specific bit 
From the Fixed Control 
Word 

0 / 1 

BV20 

FBFixedControlWord 
Bit_5 

Application Specific bit 
From the Fixed Control 
Word 

0 / 1 

BV21 

FBFixedControlWord 

Bit_6 

Application Specific bit 

From the Fixed Control 
Word 

0 / 1 

Содержание NX OPTCJ

Страница 1: ...vacon nx ac drives optcj bacnet option board user manual ...

Страница 2: ...nal resistors 9 4 4 Bus Biasing 10 5 LED indications 11 6 INSTALLATION OF VACON NX BACnet BOARD 12 7 COMMISSIONING 14 7 1 Fieldbus board parameters 14 7 2 Expander board menu M7 14 7 3 BACnet parameters 14 7 3 1 MS TP MAC address P7 x 1 1 15 7 3 2 Baud rate P7 x 1 2 15 7 3 3 Instance number P7 x 1 3 15 7 3 4 Communication status V7 x 2 1 16 7 3 5 Baud Rate V7 x 2 2 16 7 3 6 Fault V7 x 2 3 16 7 3 7...

Страница 3: ...ning control air conditioning and in heating automation The protocol is an upper level net protocol suitable for large building automation projects BACnet stands for Building Automation and Control Network BACnet is a true non propriatery open protocol communication standard conceived by a consortium of building management system users and manufacturers If you purchase your BACnet option board sep...

Страница 4: ...r and shield Electrical isolation 500 VDC Communications BACnet MS TP As described in ANSI ASHRAE Standards 135 2004 Baud rate 9600 19200 38400 and 76800 baud supports autobaud detection MAC Addresses 1 to 127 Environment Ambient operating temperature 10 C 55 C Storing temperature 40 C 60 C Humidity 95 no condensation allowed Altitude Max 1000 m Vibration 0 5 G at 9 200 Hz Safety Fulfils EN50178 s...

Страница 5: ... BACnet specific fault codes readable from panel are added from system software versions NXL NXL00005V248 VCN NXS NXS00001V163 VCN NXP NXP00002V162 VCN Communication timeout is available from system SW versions When not supported the default is 10 seconds NXL NXL00005V254 VCN NXS NXS00001V167 VCN NXP NXP00002V168 VCN OPT CJ software version OPTCJ_10522V009 and newer New baud rate 76800 from softwa...

Страница 6: ...place through the standard Vacon Interface Board Connector Figure 3 1 Vacon BACnet option board OPT CJ Signal Connector Description NC 1 No connection VP 2 Supply voltage plus 5V RxD TxD N 3 Receive Transmit data A RxD TxD P 4 Receive Transmit data B DGND 5 Data ground reference potential for VP You can use this pin 1 to bypass the cable shield to the next slave Table 3 1 OPT CJ bus connector sign...

Страница 7: ...n board has already been installed in slot D or slot E of the control board It is not necessary to detach the whole board for the grounding of the bus cable shield Just detach the terminal block 1 Strip about 5 cm of the cable and cut off the grey cable shield Remember to do this for both bus cables except for the last device See pictures below 2 Leave no more than 1 cm of the cable outside the te...

Страница 8: ...eld is connected to ground only at the last device on the net in the same way as described in chapter 4 1 Other devices of the net just pass the shield We recommend you to use an Abico connector to fit the shields into the terminal 1 Strip about 5 cm of the cable and cut off the grey cable shield Remember to do this for both bus cables except for the last device 2 Leave no more than 1 cm of the ca...

Страница 9: ...clamp See Figure 4 5 Figure 4 6 4 3 Bus terminal resistors Figure 4 8 Using jumper X4 to set the bus termination If Vacon is the last device of the fieldbus line the bus termination must be set Use jumper X4 ON position See Figure 4 7 Note Jumper X1 is only used when D9 type connector is assembled Not used with BACnet protocol Fi 4 7 ...

Страница 10: ...bus state should be neather 0 200 7V or 0 200 7V Illegal bus state is 200mV 200mV Number of nodes Bias resistance 2 5 1 8 kohm 5 10 2 7 kohm 11 20 12 kohm 21 30 18 kohm 31 40 27 kohm Table 4 1 Bias resistor size vs number of node Fail safe biasing in OPT CJ option board Connect resistor biasing resistors between pins 2 and 4 as well as pins 3 and 5 as shown in picture Matters related to this are d...

Страница 11: ... is activated and in RUN state Option board is ready for external communication Blinking slow once 5 secs Option board is activated and in FAULT state Internal fault of option board Fieldbus status LED FS GREEN LED is Meaning OFF Fieldbus module is waiting for parameters from the frequency converter No external communication ON Fieldbus module is activated Parameters received and module activated ...

Страница 12: ...on installation of bacnet board Tel 358 0 201 2121 Fax 358 0 201 212 205 6 6 INSTALLATION OF VACON NX BACNET BOARD A Vacon NX frequency converter B Remove the cable cover C Open the cover of the control unit ...

Страница 13: ...tall BACnet option board in slot E on the control board of the frequency converter Make sure that the grounding plate see below fits tightly in the clamp E Make a sufficiently wide opening for your cable by cutting the grid as wide as necessary F Close the cover of the control unit and the cable cover ...

Страница 14: ...eters associated with the expander board Enter the following menu level G with the Menu button right At this level you can browse through slots A to E with the Browser buttons to see what expander boards are connected On the lowermost line of the display you also see the number of parameter groups associated with the board If you still press the Menu button right once you will reach the parameter ...

Страница 15: ...ticular installation is determined by the value of the Max_Master property of the Device object It is recommended that MAC address 0 be reserved for use by the MS TP router and 255 is reserved for broadcasts 7 3 2 Baud rate P7 x 1 2 Select the communication speed for the network Default value is 9600 baud 0 Auto means that automatic baud rate detection is used The used Baudrate is shown in monitor...

Страница 16: ...able 7 2 below Figure 7 2 Communication status Good messages 0 999 Number of messages received without communication errors Bad Frames 0 64 Number of messages received with CRC or parity errors Table 7 2 BACnet message indications 7 3 6 Baud Rate V7 x 2 2 Shows the actual baud rate 7 3 7 Fault V7 x 2 3 Shows BACnet fault codes See Table 8 3 from Chapter 8 7 3 8 Index Nr V7 x 2 4 Shows the Device O...

Страница 17: ...ed requests supported Window Size Segmented responses supported Window Size Standard Object Types Supported An object type is supported if it may be present in the device For each standard Object Type supported provide the following data 1 Whether objects of this type are dynamically creatable using the CreateObject service 2 Whether objects of this type are dynamically deletable using the DeleteO...

Страница 18: ...cast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes No Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously ANSI X3 4 IBM Microsoft DBCS ISO 8859 1 ISO 10646 UCS 2 ISO 10646 UCS 4 JIS C 6226 If this product is a communication gateway describe the types of non BACnet equipment networks...

Страница 19: ... X X System Status X Vendor Name X Vendor Identifier X Model Name X Firmware Revision X Appl Software revision X Protocol Version X Protocol Revision X Services Supported X Object Types supported X Object List X Max APDU Length X Segmentation Support X APDU Timeout X Number ADPU Retries X Max Master X Max Info Frames X Device Address Binding X Database Revision X Preset Value X X Status Flags X X ...

Страница 20: ...ific bit from drives General Status Word 0 1 R BV10 General 3 Application specific bit from drives General Status Word 0 1 R BV11 General 4 Application specific bit from drives General Status Word 0 1 R BV12 General 5 Application specific bit from drives General Status Word 0 1 R BV13 General 6 Application specific bit from drives General Status Word 0 1 R BV14 General 7 Application specific bit f...

Страница 21: ...FixedControlWord Bit_15 Application Specific bit From the Fixed Control Word 0 1 C NOTE For Present Value Access Types R Read only W Writeable C Commandable Commandable values support priority arrays relinquish defaults 7 5 2 Analog Value Object Instance ID Object Name Description Units Present Value Access Type AV0 Frequency Setpoint Frequency Setpoint Hz R AV1 Output Frequency Output Frequency H...

Страница 22: ...ce Speed Reference percentage of nominal speed Percent C AV25 Current Limit Current Limit Amps W AV26 Min Frequency Minimum Frequency Hz W AV27 Maximum Frequency Maximum Frequency Hz W AV28 Accel Time Acceleration Time seconds W AV29 Decel Time Deceleration Time seconds W AV30 FBProcessDataIN 1 Application specific 32768 0 to 32767 0 resolution 1 0 C AV31 FBProcessDataIN 2 Application specific 327...

Страница 23: ... encoding Application Specific 3 FBFixedStatusWord MCStatus PDO 0 bit encoding B0 Ready 0 not ready 1 ready B1 Run 0 stopped 1 running B2 Direction 0 clockwise 1 counterclockwise B3 Fault 1 the FC is faulted and stopped B4 Warning 1 warning B5 AtReference 1 at reference speed B6 ZeroSpeed 1 at zero speed B7 FluxReady 1 flux ready B8 TCSpeedLimitActive B9 DetectedEncoderDirection B10 UVFastStop B11...

Страница 24: ...on distributor Check that MAC ID is unique 54 Slot fault Defective option board or slot Check the board and slot Contact the nearest Vacon distributor Table 8 1 RS 485 option board faults You can define with parameters how the frequency converter shall react to certain faults Code Parameter Min Max Unit Step Default ID Note P2 7 22 Response to fieldbus fault 0 3 1 0 733 0 No response 1 Warning 2 F...

Страница 25: ...and BACnet stack on the option board uses files from BACnetSim a GPL d project on SourceForge The licence for BACnetSim is GPL with a special exception that allows linking without requiring the rest of the code to be GPL d The source code for the GPL d parts can be downloaded from SourceForge ...

Страница 26: ... vacon com Vacon Plc Runsorintie 7 65380 Vaasa Finland Subject to change without prior notice 2012 Vacon Plc Find your nearest Vacon office on the Internet at www vacon com Find your nearest Vacon service centre on the Extranet at www extra vacon com ...

Отзывы: