commissioning
vacon • 21
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
BV22
FBFixedControlWord
Bit_7
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV23
FBFixedControlWord
Bit_8
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV24
FBFixedControlWord
Bit_9
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV25
FBFixedControlWord
Bit_10
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV26
FBFixedControlWord
Bit_11
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV27
FBFixedControlWord
Bit_12
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV28
FBFixedControlWord
Bit_13
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV29
FBFixedControlWord
Bit_14
Application Specific bit
From the Fixed Control
Word
0 / 1
C
BV30
FBFixedControlWord
Bit_15
Application Specific bit
From the Fixed Control
Word
0 / 1
C
NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.
7.5.2
Analog Value Object
Instance ID
Object Name
Description
Units
Present Value
Access Type
AV0
Frequency Setpoint
Frequency Setpoint
Hz
R
AV1
Output Frequency
Output Frequency
Hz
R
AV2
Motor Speed
Motor Speed
Rpm
R
AV3
Load (power)
Motor Shaft Power
Percent
R
AV4
Kilowatt Hours total
Megawatt Hour Counter
(Total)
kWh
R
AV5
Motor Current
Motor Current
Amps
R
AV6
DC link Voltage
DC link Voltage
Volts
R
AV7
Motor Voltage
Motor Voltage
Volts
R
AV8
Unit Temperature
Heatsink Temperature
NOT IN NXL -series
°
C
R
AV9
Motor Torque
In % of motor nominal
Torque
Percent
R
AV10
Operating Days
Operating Days
(resettable)
Day
R
AV11
Operating Hours
Operating Hours
(resettable)
Hour
R
AV12
Kilowatt Hours
Kilowatt Hours
(resettable)
kWh
R
AV13
Torque Reference
Torque Reference NOT
IN NXL -series
Percent
R