Page 6 (15)

Vacon

I/O-expander board installation (Vacon CXS-range)

Vacon Plc

Tel:

+358-201 2121

Fax:

+358-201 212 205

Service:

+358-40-8371 150

E-mail:

[email protected]
http://www.vacon.com

Table 3-2.

I/O-expander board installation (continues ...).

1

2

4

Remove the control panel, control panel base (4 screws) and the jumper X4 from the
control board.

3

3.2

INSTALLATION

I/O-repeater board (1) should be installed above the control board inside the frequency con-
verter. The I/O-expander board (10) and I/O-interface board (11) should be installed in the
option box. Follow the instructions below (see Table 3-2).

Check that the jumper for I/O-repeater board 

(1)

 is in the right position in terminal X5 

(3)

.

The position of the jumper must be chosen according to the I/O-expander board 

(11)

:

- If I/O-expander board CX101OPT or 103OPT

is in use, jumper must be in position A.

- If I/O-expander board CX100OPT or 102OPT

is in use, jumper must be in position B.

- If one of the following fielbus boards is in use:

CX200OPT, CX201OPT, CX202OPT or
CX203OPT, jumper must be in position C.
(Positon D is not in use).

X5

X4

Make sure that the cable of the control panel
cover is connected to the control board X1 ter-
minal. Connect the 4-pole power cable 

(4)

 to

the control board X5 terminal (The power cable
can also be connected to the X6-terminal, if the
power cable from the power board is connected
to the X5-terminal.)
Set the protection foil 

(5)

 above the control

board  as shown in the picture. Make sure that
the protection foil is correctly located, the hole
in the foil will must be located above the stand
sleeve.

 X5

Remove the fixing screw from the control board
and replace it with the stand sleeve 

(7)

.

5

7

Содержание CXS Series

Страница 1: ...O O T H C O N T R O L I O e x p a n d e r b o a r d i n s t a l l a t i o n m a n u a l Va c o n C X S r a n g e Subject to changes without notice V A C O N C X C X L C X S F R E Q U E N C Y C O N V E...

Страница 2: ...acon com CONTENTS 1 GENERAL 2 1 1 Vacon CX100OPT 2 1 2 Vacon CX101OPT 2 1 3 Vacon CX102OPT 2 1 4 Vacon CX103OPT 2 1 5 Vacon CX104OPT 3 1 6 Vacon fieldbus boards 3 2 SPECIFICATIONS 4 3 INSTALLATION 5 3...

Страница 3: ...tor Control 1 2 Vacon CX101OPT The available I O can be increased by using the Vacon CX101OPT I O expander board 5 digital inputs standard signals relay output standard signal thermistor input can be...

Страница 4: ...O expander board encoder input Typical use Closed Loop Vector Control 1 6 Fieldbus boards Vacon fieldbus boards can be installed in the Vacon CXS range frequency converters as I O expander boards The...

Страница 5: ...Ri 330 Table 2 1 Specifications All the control connections are not found on every I O expander board for specific information see Chapters 1 and 4 The control connections are isolated from the mains...

Страница 6: ...I O expander board 11 check that the typecode is corresponds to your order I O interface board 12 10 pole data cable 13 4 pole power cable 14 screws for I O expander board 15 screws for I O interface...

Страница 7: ...g to the I O expander board 11 If I O expander board CX101OPT or 103OPT is in use jumper must be in position A If I O expander board CX100OPT or 102OPT is in use jumper must be in position B If one of...

Страница 8: ...correctly located push the arms of the protection foil under the control panel cover Fasten the I O repeater board and protection foil to the stand sleeve 7 with the screw X14 Install the control pane...

Страница 9: ...Note the jumper can be connected in ON or OFF position see Vacon CX CXL CXS User s manual Chapter 6 2 2 13 If you have the option box with the I O expander 11 and I O interface boards 12 pre installe...

Страница 10: ...l for more specific information X8 16 If an encoder input closed loop control is to be used and the encoder works at a 5V level move three jumpers from terminal X5 to terminal X8 If the encoder works...

Страница 11: ...1 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Figure 3 2 Frequency converter and external I O expander box installation unit sizes M3 and M4B I O expande...

Страница 12: ...Contact open no fault closing contact Contact closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 sel...

Страница 13: ...t closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 select...

Страница 14: ...tor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no actio...

Страница 15: ...V 209 DIC1 External fault Contact open no fault closing contact Contact closed fault 210 DIC2 Run disableCont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel tim...

Страница 16: ...ND I O ground Ground for controls 206 24V Control voltage output 207 GND I O ground Ground for controls 214 DI6A Pulse input A 215 DI6A differential input 216 DI7B Pulse input B 217 DI7B differential...

Страница 17: ...V ACONPLC P O Box 25 Runsorintie 7 FIN 65381 VAASA FINLAND Phone 358 201 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Distributor U D 00244C1 19 10 2000...

Отзывы: