Vacon
Page 13 (15)
I/O-expander board installation (Vacon CXS-range)
Vacon Plc
Tel:
+358-201 2121
Fax:
+358-201 212 205
Service:
+358-40-8371 150
E-mail:
[email protected]
http://www.vacon.com
Terminal
Signal
Description
201
+10V
ref
Reference output
Voltage for a potentiometer, etc.
202
U
i n
+
Analogue input, voltage
Not in use
range 0—10 V DC
203
GND
I/O ground
Ground for reference and controls
204
U
i n
+
Analogue input, voltage
Not in use
205
U
i n
-
range 0—10 V DC
206
+24V
Control voltage output
Voltage for switches, etc. max. 50 mA
207
GND
I/O ground
Ground for reference and controls
208
CMC
Common for DIC1-DIC5
Connect to GND or + 24 V
209
DIC1
External fault
Contact open = no fault
(closing contact)
Contact closed = fault
210
DIC2
Run disable
Cont. open = start of motor enabled
Cont. closed= start of motor disabled
211
DIC3
Acceler. / Decel. time
Contact open = time 1 selected
selection
Contact closed = time 2 selected
212
DIC4
Jogging speed selection
Contact open = no action
Contact closed = jogging speed
213
DIC5
Fault reset
Contact open = no action
Contact closed = fault reset
214
DI6A+
Pulse input A
215
DI6A-
(differential input)
216
DI7B+
Pulse input B
90 degrees phase shift compared
217
DI7B-
(differential input)
to pulse input A
218
DO1
Encoder direction output
219
DO2
Encoder divider 1/64 output
220
U
out
+
Analogue output
Programmable
0—10 V DC/R
L
≥
1 k
Ω
(Motor voltage as default value)
221
T I +
Thermistor input
222
T I -
223
RO3/1
Relay output 3
READY
224
RO3/2
225
RO4/1
Relay output 4
RUN
226
RO4/2
227
RO5/1
Relay output 5
FAULT
228
RO5/2
4.3
Vacon CX102OPT
Figure 4-3 Control connections of Vacon CX102OPT.
Signal from
motor thermistors *)
*) NOTE!
Thermistor input (terminals 221 and 222) must be shorted if not used.
Enco-
der