Page 4 (15)

Vacon

I/O-expander board installation (Vacon CXS-range)

Vacon Plc

Tel:

+358-201 2121

Fax:

+358-201 212 205

Service:

+358-40-8371 150

E-mail:

[email protected]
http://www.vacon.com

2

SPECIFICATIONS

Safety

Fulfills EN50178, C-UL and EN60204-1 standards

Control

Analogue voltage, input

0—± 10 V, R

 200 k

connections

Analogue current, input

0(4)—20 mA, R

i

  = 250 

Digital input

24 V: "0" 

10 V, "1" 

18 V, R

i

 > 5 k

Aux. voltage

24 V (±20%), max. 50 mA

Reference voltage

10 V ±3 %, max. 10 mA

Analogue current, output

0(4)—20 mA, R

L

  = 500 

 , resolution 10 bit,

 accuracy 

±2%

Analogue voltage, output 0(2)—10 V, R

L

 

 1 k

 , resolution 10 bit,

 accuracy 

±2%

Relay  output

Max. switching voltage:

300 V DC, 250 V AC

Max. switching load:

8A / 24 V DC
0,4 A / 300 V DC
2 kVA / 250 V AC

Max. continuous load:

2 A rms

Thermistor input

R

trip

 = 4.7 k

Encoder input

24 V: "0" 

10 V, "1" 

18 V, R

i

 = 2.2 k

5 V:   "0" 

 2 V, "1" 

 3 V, R

i

 = 330 

Table 2-1 Specifications. (All the control connections are not found on every I/O-expander board, for
specific information see Chapters 1 and 4.)

The control connections are isolated from the mains potential and the I/O ground is
connected to the frame of the inverter via a 1-M

 resistor and 4,7-nF capacitor*). The

control I/O ground can be connected directly to the frame by changing the position of the
jumper X4 (GND ON/OFF) to the ON-position. Digital inputs and relay outputs are also
isolated from the I/O ground.

*) Default value (X4 is GND OFF- position).

    NOTE!

Internal components and circuit boards (except the isolated I/O terminals) are at
mains potential when the frequency converter is connected to the mains. This
voltage is extremely dangerous and may cause death or severe injury if you
come into contact with it.

The control I/O terminals are isolated from the mains potential, but the relay
outputs and other I/O's may have a dangerous voltage connected even if the
power is disconnected from the frequency converter.

Содержание CXS Series

Страница 1: ...O O T H C O N T R O L I O e x p a n d e r b o a r d i n s t a l l a t i o n m a n u a l Va c o n C X S r a n g e Subject to changes without notice V A C O N C X C X L C X S F R E Q U E N C Y C O N V E...

Страница 2: ...acon com CONTENTS 1 GENERAL 2 1 1 Vacon CX100OPT 2 1 2 Vacon CX101OPT 2 1 3 Vacon CX102OPT 2 1 4 Vacon CX103OPT 2 1 5 Vacon CX104OPT 3 1 6 Vacon fieldbus boards 3 2 SPECIFICATIONS 4 3 INSTALLATION 5 3...

Страница 3: ...tor Control 1 2 Vacon CX101OPT The available I O can be increased by using the Vacon CX101OPT I O expander board 5 digital inputs standard signals relay output standard signal thermistor input can be...

Страница 4: ...O expander board encoder input Typical use Closed Loop Vector Control 1 6 Fieldbus boards Vacon fieldbus boards can be installed in the Vacon CXS range frequency converters as I O expander boards The...

Страница 5: ...Ri 330 Table 2 1 Specifications All the control connections are not found on every I O expander board for specific information see Chapters 1 and 4 The control connections are isolated from the mains...

Страница 6: ...I O expander board 11 check that the typecode is corresponds to your order I O interface board 12 10 pole data cable 13 4 pole power cable 14 screws for I O expander board 15 screws for I O interface...

Страница 7: ...g to the I O expander board 11 If I O expander board CX101OPT or 103OPT is in use jumper must be in position A If I O expander board CX100OPT or 102OPT is in use jumper must be in position B If one of...

Страница 8: ...correctly located push the arms of the protection foil under the control panel cover Fasten the I O repeater board and protection foil to the stand sleeve 7 with the screw X14 Install the control pane...

Страница 9: ...Note the jumper can be connected in ON or OFF position see Vacon CX CXL CXS User s manual Chapter 6 2 2 13 If you have the option box with the I O expander 11 and I O interface boards 12 pre installe...

Страница 10: ...l for more specific information X8 16 If an encoder input closed loop control is to be used and the encoder works at a 5V level move three jumpers from terminal X5 to terminal X8 If the encoder works...

Страница 11: ...1 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Figure 3 2 Frequency converter and external I O expander box installation unit sizes M3 and M4B I O expande...

Страница 12: ...Contact open no fault closing contact Contact closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 sel...

Страница 13: ...t closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 select...

Страница 14: ...tor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no actio...

Страница 15: ...V 209 DIC1 External fault Contact open no fault closing contact Contact closed fault 210 DIC2 Run disableCont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel tim...

Страница 16: ...ND I O ground Ground for controls 206 24V Control voltage output 207 GND I O ground Ground for controls 214 DI6A Pulse input A 215 DI6A differential input 216 DI7B Pulse input B 217 DI7B differential...

Страница 17: ...V ACONPLC P O Box 25 Runsorintie 7 FIN 65381 VAASA FINLAND Phone 358 201 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Distributor U D 00244C1 19 10 2000...

Отзывы: