7-segment Control panel
6.
Programmable push-button page
The BTNS indicator is lit when the
programmable push button page is active. The
function of the enter button can be selected on
this page. The selected function is valid only
on this page and on other pages the enter
button has it’s original function. The feedback
information tells the state of the button
function. When the button is pressed, the
feedback information is shown small.
Figure 9. Programmable push button page.
RUN READY FAULT
MON PAR REF BTNS
RUN READY FAULT
MON PAR REF BTNS
Push down
Release
The feedback information
is shown small when the
button is pushed
The feedback information
changes its state as soon
as "push down" has been
recognized
The feedback information
is shown big when
the button is released
Feedback
information
MON PAR REF BTNS
RUN READY FAULT
MON PAR REF BTNS
RUN READY FAULT
MON PAR REF BTNS
RUN READY FAULT
Button-page
Button no.
Button
Button
Function
Feedback information
number
name
0
1
Note
b 1
Reverse
Changes the direction
Direction
Direction
Feedback information
of rotation of the motor .
command
command
flashes as long as
Active only if the panel is
forward
reverse
direction is different
the active control source
from the command
b 2
Active
Selects the active control
Control via
Control from the
control
source between the
I/O terminals
Control Panel
source
panel and I/O terminals
b 3
Clear trip
When pressed clears
No clearing
Clearing accepted
operating
the trip operating hour
hour
counter
counter
b 4
Clear trip
When pressed clears
No clearing
Clearing accepted
MWh
the MWh trip counter
counter
Table 2. Programmable push-buttons.