Page 9 (10)

7-segment Control panel

9.

Active warning display

When a warning occurs a symbol "

A " appears

on the display together with a blinking warning
code. See Figure 12. Warning codes are
explained in Table 3.

The display can be cleared with the PG (Page)

button and the display returns to the state
before the warning* appeared. If the cause of
the warning stays active, a new warning is not
given for 1 minute.

* The warning will be automatically cleared after 1
minute.

RUN              READY              FAULT

MON         PAR         REF        BTNS

PG

RUN             READY               FAULT

MON         PAR         REF        BTNS

RUN              READY              FAULT

MON         PAR         REF        BTNS

Warning 
code blinks

Figure 12. Warning code display.

Warning codes:

Code

Warning

Checking

A  15

Motor stalled (Motor stall protection)

Check motor

A  16

Motor over temperature (Motor thermal protection)

Decrease motor loading

A  17

Motor underload

Check motor loading

(Warning can be activated in "Five in One" applications)

A  24

The values in the Fault history, MWh-counters or

Does not need any actions

operating day/hour counters might have been

Take a critical attitude to these

changed in a previous mains interruption.

values

A  28

The change of an application has failed

Choose the application again and
Push Enter-button

A  30

Onbalance current fault, the load of the segments is

Contact nearest Vacon distributor

not equal.

A  45

Vacon frequency converter overtemperature warning,

Check the cooling air flow and

temperature >70°C

the ambient temperature

A  46

Reference warning, the current of input  I

in+

 <4 mA

Check the current loop

(Warning can be activated in "Five in One" applications) circuitry

A  47

External warning

Check the external fault circuit or

(Warning can be activated in "Five in One" applications) device

Table 3. Warning codes.

Содержание 7-segment Control Panel

Страница 1: ...V ACON CX CXL CXS FREQUENCY CONVERTERS 7 segment Control Panel Subject to changes without notice F O R S M O O T H C O N T R O L ...

Страница 2: ...ge 6 5 Reference page 6 6 Programmable push button page 7 7 Fault history page 8 8 Active fault display 8 9 Active warning display 9 10 Controlling the motor from the front panel 10 10 1 Control source change from I O terminal to front panel 10 10 2 Control source change from control panel to I O terminal 10 ...

Страница 3: ...ions and problems with Vacon CX CXL CXS frequency converter please refer to the CX CXLCXS User s Manual or the Five In One Application Manual DRIVE STATUS INDICATORS RUN lights when the motor is running READY lights when mains voltage has been applied and the drive is ready to operate FAULT lights if fault occurs DISPLAY Displays parameter values monitoring data etc six digits ACTIVE MENU PAGE IND...

Страница 4: ...N PAR REF BTNS RUN READY FAULT RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PA...

Страница 5: ...or power Calculated actual power nominal power of the unit n 6 Motor voltage V Calculated motor voltage n 7 DC link voltage V Measured DC link voltage n 8 Temperature C Temperature of the heat sink n 9 Operating day counter DD dd Operating days 1 not resettable n 10 Operating hours trip HH hh Operating hours 2 can be reset with program counter mable button 3 n 11 MW hours MWh Total MW hours not re...

Страница 6: ...igure 6 Output signal status Figure 5 Digital inputs Group B status Example Input Terminal DIB4 14 closed DIB5 15 open DIB6 16 closed Example Output Terminal Digital output 20 closed sinking current Relay output 1 21 open Relay output 2 24 open MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT 0 open input 1 closed input active MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN ...

Страница 7: ...PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT Increment value Decrement value Confirm value Next page Parameter value Parameter page Parameter group Parameter number The reference change is valid immediately The motor speed changes as fast as the reference is changing or the load inertia allows the motor to accelerate decelerate The active control s...

Страница 8: ...s its state as soon as push down has been recognized The feedback information is shown big when the button is released Feedback information MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT MON PAR REF BTNS RUN READY FAULT Button page Button no Button Button Function Feedback information number name 0 1 Note b 1 Reverse Changes the direction Direction Direction Feedback information...

Страница 9: ...lained in Chapter 9 of the Vacon CX CXLCXS User s Manual The display can be cleared with the Page button PG The read out returns to the same display it had before the trip The fault remains active until it is cleared with the Reset button RST or with the reset signal from the I O terminal See figure 11 Note Remove external Start signal before resetting a fault RUN READY FAULT MON PAR REF BTNS RUN ...

Страница 10: ...ction Check motor A 16 Motor over temperature Motor thermal protection Decrease motor loading A 17 Motor underload Check motor loading Warning can be activated in Five in One applications A 24 The values in the Fault history MWh counters or Does not need any actions operating day hour counters might have been Take a critical attitude to these changed in a previous mains interruption values A 28 Th...

Страница 11: ...The direction of rotation remains the same as with I O control If the Start button is pushed at the same time as the programmable push button b2 the Run state direction of rotation and reference value will be copied from the I O terminals to the front panel 10 2 Control source change from panel to I O terminals After changing the control source the I O terminals determine the run state direction o...

Страница 12: ...ud00351b p65 13 10 2000 Vacon Plc P O Box 25 Runsorintie 7 65381 VAASA Tel 358 0 201 2121 Fax 358 0 201 212 205 On call 358 0 40 8371 150 E mail vacon vacon com http www vacon com ...

Отзывы: