Safety
In VACON
®
20 X, the phase conductor and the corresponding protective earthing conductor
can be of the same cross-sectional area, provided they are made of the same metal (because
the cross-sectional area of the phase conductor is less than 16 mm
2
).
The cross-sectional area of every protective earthing conductor which does not form a part of
the supply cable or cable enclosure shall, in any case, be not less than:
•
2.5 mm
2
if mechanical protection is provided or
•
4 mm
2
if mechanical protection is not provided. For cord-connected equipment, provi-
sions shall be made so that the protective earthing conductor in the cord shall, in the
case of failure of the strain-relief mechanism, be the last conductor to be interrupted.
However, always follow the local regulations for the minimum size of the protective earthing
conductor.
NOTE:
Due to the high capacitive currents present in the AC drive, fault current protective
switches may not function properly.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание 20 x
Страница 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 18: ...vacon 15 Receipt of delivery 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 24: ...3 vacon 21 Mounting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 32: ...4 vacon 29 Power cabling Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 46: ...5 vacon 43 Control unit Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 54: ...6 vacon 51 Commissioning Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 70: ...8 vacon 67 Options Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...