Safety
vacon • 4
1
1.3
Earthing and earth fault protection
The VACON
®
20 X AC drive must always be earthed with an earthing conductor connected to
the earthing terminal marked with
.
Since the touch current exceeds 3.5 mA AC, according to EN61800-5-1, the drive shall have a
fixed connection and provision of an additional terminal for a second protective earthing con-
ductor of the same cross-sectional area as the original protective earthing conductor.
Three screws are provided for: the ORIGINAL protective earthing conductor, the SECOND pro-
tective conductor and the MOTOR protective conductor (the customer can choose the screw for
each one). See Figure 1 for the location of the three screws in the two possible options avail-
able.
Figure 1. Protective earthing connections.
CAUTION!
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание 20 x
Страница 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 18: ...vacon 15 Receipt of delivery 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 24: ...3 vacon 21 Mounting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 32: ...4 vacon 29 Power cabling Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 46: ...5 vacon 43 Control unit Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 54: ...6 vacon 51 Commissioning Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 70: ...8 vacon 67 Options Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...