Commissioning
vacon • 46
6
6.2
Changing EMC protection class
The EMC protection class of Vacon 20 X can be changed from class C2 to class C4. This is done
as described below:
6.2.1
Changing EMC protection class - MU2
Figure 29.Changing of the EMC class in MU2 control unit.
Warning! Do not perform any modifications on the AC drive when it is connected
to mains.
1
Remove the three screws on the EMC plate from the unit.