7. GENERAL DATA
- With above-mentioned fuses, the drive can be connected to power supply the short
circuit current of which is max. 50kA
- Use cables with heat resistance of at least +70 C.
- The fuses function also as cable overload protection.
Dimensions
and weight
Frame
Height Width Depth (mm) Weight (kg)
MI1
156,5 65,5 98,5 0,55
MI2
195 90 101,5 0,70
MI3
262,5 100 108,5 0,99
Supply network
Networks
Vacon 10 480 V cannot be used with corner grounded networks
Short circuit current
Maximum short circuit current has to be < 50kA
Motor
connection
Output voltage
0 - U
in
Output current
Continuous rated current I
N
at ambient temperature max. +50ºC, over-
load 1.5 x I
N
max. 1min/10min
Ambient
conditions
Ambient operating
temperature
-10°C (no frost)…+50°C: rated loadability I
N
Storage temperature
-40°C…+70°C
Enclosure class
IP20
Relative humidity
0…95% RH, non-condensing, non-corrosive, no dripping water
Altitude
100% load capacity (no derating) up to 1000m. 1% derating for each
100m above 1000m; max. 2000m
EMC
Immunity
Complies with EN50082-1, -2, EN61800-3
Emissions
230V : Complies with EMC category C2 (Vacon level H); With an internal
RFI filter
400V: Complies with EMC category C2 (Vacon level H): With an internal
RFI filter
Both: No EMC emission protection (Vacon level N): Without RFI filter
See detailed descriptions in Vacon 10 User Manual at:
www.vacon.com/support
Standards
For EMC: EN61800-3,
For safety: UL508C, EN61800-5-1
Certificates
and manufac-
turer’s decla-
rations of
conformity
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
Cable and fuse require-
ments
380 - 500V
Frame
Fuse
(A)
Mains cable
Cu (mm
2
)
Terminal cable min-max (mm
2
)
Main & earth
Control & relay
MI1
6
3*1.5+1.5
1.5-4
0.5-1.5
MI2
10
MI3
20
3*2.5+2.5
1.5-6
208 - 240V
MI1
10
2*1.5+1.5
1.5-4
MI2
20
2*2.5+2.5
MI3
32
2*6+6
1.5-6