background image

navigation & startup 

vacon 

 8

24-hour s358 (0)40 837 1150 • Email: [email protected]

4

4.3  Selection of control place or fieldbus address

In Vacon 10 RS-485 the user can select the control place and Modbus slave address 
without connecting the drive to PC. The procedures are described below.

4.3.1  Selection of control place

NOTE!

 When keypad is selected as the control place, Vacon RS-485 starts forward 

when the START button is pressed. The frequency reference can be increased for 
5Hz with each press of the button.

Green

Green

Red

Press the STOP button for 5 seconds in STOP state,

the READY and FAULT LEDs start to blink in turns:

Press the STOP-button to

proceed to the next step

1)

2)

Keypad control place selection, all LEDs are off

3)

PRESS

The keypad is now the control place and frequency

reference source of the drive and the drive is ready for

operation.

Содержание 10

Страница 1: ......

Страница 2: ...s con nected to mains even if the motor is not running The control I O terminals are isolated from the mains poten tial However the relay output terminals may have a danger ous control voltage present...

Страница 3: ...crew or DIN rail mounting Figure 1 Screw mounting left and DIN rail mounting right NOTE See the mounting dimensions on the back of the drive Leave free space for cooling above 100 mm and below 50 mm V...

Страница 4: ...bles is 0 5 0 6 Nm Figure 3 Vacon 10 power connections MI1 Figure 4 Vacon 10 power connections MI2 MI3 1 230V 3 400V Motor out MAINS MOTOR Strip the plastic cable coating for 360 earthing L1 L2 N L3 U...

Страница 5: ...pport 358 0 40 837 1150 Email vacon vacon com 2 2 2 2 Control cabling Figure 5 Open the cover Figure 6 Install the control cables See next page Strip the plastic cable coating for 360 earthing Control...

Страница 6: ...Vacon 10 RS 485 I O terminals Terminal Signal Factory preset Description 3 GND I O signal ground 6 24Vout 24V output for DI max load 50 mA 7 GND I O signal ground 8 DI1 Digital input 1 1 Start forward...

Страница 7: ...indicate the status of the drive provide the user with information on faults and help the user to select the control place or fieldbus address Figure 1 The status LEDs of Vacon 10 RS 485 The followin...

Страница 8: ...switch is in STOP posi tion 5 Connect the drive to mains 6 This step is not valid for API RS 485 7 Perform test run without motor see the User Manual at www vacon com 8 Run no load tests without motor...

Страница 9: ...When keypad is selected as the control place Vacon RS 485 starts forward when the START button is pressed The frequency reference can be increased for 5Hz with each press of the button Green Green Red...

Страница 10: ...ddress selection The slave addresses are binary coded and indicated with blinking LEDs Press the STOP button to move to the next address 4 Address 1 Address 2 Address 3 Address 4 Address 5 Address 6 A...

Страница 11: ...of the motor M1 6 Motor power 5 Calculated actual nominal power of the motor M1 7 Motor voltage V 6 Motor voltage M1 8 DC link voltage V 7 Measured DC link voltage M1 9 Unit temperature C 8 Heat sink...

Страница 12: ...nit 107 P1 15 Torque boost 0 1 0 109 0 Not used 1 Used P2 1 Control place 1 3 3 125 1 I O terminal 2 Keypad 3 Fieldbus P2 2 Start function 0 1 0 505 0 Ramp 1 Flying start P2 3 Stop function 0 1 0 506...

Страница 13: ...r of error messages yyy 0 999 Number of good messages S2 2 Fieldbus protocol 0 1 1 809 0 FB disabled 1 Modbus S2 3 Slave address 1 255 810 S2 4 Baud rate 0 5 5 811 0 300 1 600 2 1200 3 2400 4 4800 5 9...

Страница 14: ...rt pulse long pulse Red LED blinking sequence Fault code Fault name 1 Overcurrent 2 Overvoltage 3 Earth fault 8 System fault 9 Undervoltage 13 Frequency converter undertempera ture 14 Frequency conver...

Страница 15: ...torage temperature 40 C 70 C Enclosure class IP20 Relative humidity 0 95 RH non condensing non corrosive no dripping water Altitude 100 load capacity no derating up to 1000m 1 derating for each 100m a...

Страница 16: ...0 contin current IN A 150 overload current A P kW A Vacon 10 1L 0001 2 1 7 2 6 0 25 4 2 MI1 Vacon 10 1L 0002 2 2 4 3 6 0 37 5 7 MI1 Vacon 10 1L 0003 2 2 8 4 2 0 55 6 6 MI1 Vacon 10 1L 0004 2 3 7 5 6 0...

Страница 17: ......

Страница 18: ...Bentsrudveien 17 3080 Holmestrand telephone 47 330 96120 fax 47 330 96130 romania Vacon Romania Reprezentanta Cuza Voda 1 400107 Cluj Napoca Tel 40 364 118 981 Fax 40 364 118 981 russia ZAO Vacon Driv...

Отзывы: