ENGLISH
- 37 -
PARAMETER
VALUE
DESCRIPTION
DEFAULT
MEMO
t.APP
Partial opening time (pedestrian access)
6.0”
0.0”-1’00
When the control unit receives a Start Pedestrian command, it will open
leaf 1 only, for a shorter time. Max allowed time to be setup is
t.AP1
t.Ch1
Leaf 1 closing time
23.5”
0.0”-5’00
Tempo regolabile da 0 secondi a 5 minuti
NOTA
: Per evitare che l’anta non si chiuda completamente, è consigliabile
impostare un tempo più lungo di quello di apertura
t.AP1
t.Ch2
Tempo di chiusura anta 2
23.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes.
NOTE
: To avoid that the door does not close completely, we recommend
to setup a longer time than
t.AP2
opening time.
t.ChP
Partial closing time (pedestrian access)
7.0”
0.0” - 2’00
When the control unit receives a Start Pedestrian command, it will use this
time to close the gate. Max allowed time to be setup is
t.Ch1
.
NOTE
: To avoid that the door does not close completely, we recommend
to setup a longer time than
t.APP
opening time
t.C2P
Leaf 2 closing time during pedestrian cycle
no
0.5” - 5.0”
During a partial opening cycle (pedestrian access) leaf 2 may move slightly
because of the wind or its own weight; in this case at closing time leaf 1
could hit leaf 2 and the gate would remain not perfectly closed.
To avoid this, in the last seconds of the cycle a light closing force is applied
to leaf 2 too.
no
Function deactivated
r.AP
Opening door delay
1.0”
0.0” - 1’00
During the opening phase, leaf 1 must start moving before leaf 2, to avoid
that both doors may collide.
Leaf 2 opening will be delayed for the setup time
r.Ch
Closing door delay
3.0”
0.0” - 1’00
During the closing phase, leaf 1 must start moving after leaf 2, to avoid
that both doors may collide.
Leaf 1 closing will be delayed for the setup time
t.SEr
Lock time
2.0”
0.5”- 1’00
Before the opening phase begins, the control unit will energize the electric
lock in order to release it and enable the gate motion.
t.SEr
time will fix
the energizing time.
m
WARNING: in case the gate has no electric lock, set the value
no
no
Function deactivated
SEr.S
Silent Locking Mode
Si
Si
Function activated
no
Function deactivated
t.ASE
Lock advance time
1.0”
0.0”- 1’00
While the electric lock is energized, the gate will stay standstill for
t.ASE
time, to make its release easier.
In case
t.ASE
is lower than
t.SEr
, the lock energizing will go on while
the doors will start moving.
m
WARNING
: in case the gate has no electric lock, set the value
0.0”