Installation instructions
Heat pump dryer
Multi-family building
J173.113-0
6.4.11 ITH
2
➤
Open the appliance door.
– The identification plate is located on the top of the front panel.
The necessary installation accessories are located in the drum.
Installation plate (W3.0035)
The room must be well ventilated to ensure that the room temperature does not exceed 35 °C.
If the volume of the room in which the appliance is located is min. 40 m³ when closed:
Condensation may form on thermal bridges!
The room must be aired (by opening the door or a window in the room) between consecutive drying programmes!
If the volume of the room in which the appliance is located is <40 m³:
There must be air inlet and outlet openings (open window, ventilation grille or slits in the door, ventilation system) to the adjacent room
or to the outside.
Identification plate
Installation accessories supplied
Designation
Article no.
Pieces
See installation step
Condensate drain kit
W5.1346
1
3. Connect condensate drain
Room conditions/ventilation
Do not obstruct the appliance’s ventilation slits to ensure that there is an ample supply of air.
The room temperature should be kept as low as possible to ensure the appliance runs efficiently. A room temperature of under
35 °C is critical otherwise this prolongs the duration of the programmes.