TABLE 13a : BECKETT CHIMNEY VENT PRELIMINARY BURNER SETTINGS
Boiler
Model
Head
Type
Static
Plate
Insertion
Dept
[inch]
Firing
Rate
[GPH]
Com
-
bustion
Liner
Nozzle
Mftr.
Nozzle Type
Pump
Pressure
[PSI]
Head
Setting
Air
Band
Air
Shutter
Rated AFUE
Efficiency
[%]
4075
L2
3.375U
2.625
0.75
Oval
Delavan
0.65x60B
140
N/A
0
7
87.0
4090
L2
3.375U
2.625
0.9
Oval
Delavan
0.75x60B
140
N/A
0
10
86.0
5100
L1
None
2.625
1.00
None
Delavan
0.75 x 60B
175
N/A
0
7
87.0
5120
L1
None
2.625
1.20
None
Delavan
0.90 x 60W
175
N/A
2
8
86.0
6130
V1-0
2.75M
2.625
1.30
V6
Delavan
1.0 x 60B
175
0
1
10
87.0
6145
V1-1
2.75M
2.625
1.45
V6
Delavan
1.10 x 60B
175
1
2
7
86.0
7165
V1
2.75M
2.625
1.65
V7
Hago
1.25 x 45B
175
2
4
10
87.0
7180
V1
2.75M
2.625
1.80
V7
Hago
1.35 x 45B
175
3
3
10
86.0
Timings
Pre-purge
15 seconds
Post-purge
15 seconds
Table 13 - Beckett Chimney Vent Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
TABLE 13B: BECKETT /ECR PART NUMBERS
Boiler
Model
Beckett Oil
Burner
Model
ECR Oil
Burner Part
Number
with Cover
ECR Oil
Burner Part
Number
Less Cover
4075
AFG70MQASN
240007144
240007232
4090
AFG70MQASN
240013302
240013303
5100
AFG70MSASN
240013394
240013393
5120
AFG70MSASN
240013396
240013395
6130
AFG70MKAQN
240013398
240013397
6145
AFG70MKAQN
240013400
240013399
7165
AFG70MKASN2
240013402
240013401
7180
AFG70MKASN2
240013404
240013403
17 - OIL BURNER, NOZZLE, & AIR SETTINGS