applications,  such  as  solenoid  activated  valves,  an 

external power supply can be used.  The R1425 monitors 

its own internal circuits, and the status of external input 

devices.  The R1425 also monitors detonators that are 

connected  to  it  for  opens,  shorts  to  ground,  and  low 

voltage  conditions.    System  status  is  shown  on  front 

panel indicators.  See Figure 4.

w2400 gROUND FaULT mONITOR mODULE

The W2400 Ground Fault Monitor is a dedicated module 

in the Flame Detection/Releasing System that protects 

the integrity of the system power wiring by monitoring 

for ground faults.  Detection of a ground fault condition 

is  indicated  by  actuation  of  a  solid  state  output  and 

illumination of LEDs on the faceplate of the module.

1

RED ALARM RELAY LED, NORMALLY OFF—BLINKS WHEN RELAY ENERGIZED, ON (STEADY) WHEN RELAY DE-ENERGIZED, (ALARM ACCEPT)

2A

SELECT/ALARM ACCEPT BUTTON—IN NORMAL MODE, DE-ENERGIZES ALARM RELAY – IN TEST MODE, SELECTS NEXT RELAY CIRCUIT 

FOR TEST

2B

SELECT BUTTON—SELECTS RELAY CIRCUIT IN TEST MODE

3

DIGITAL DISPLAY—NORMALLY OFF—TURNS ON TO INDICATE STATUS CHANGE AND RELAY AFFECTED

4

AMBER SYSTEM FAULT LED, NORMALLY OFF—ON TO INDICATE SYSTEM FAULT

5

GREEN POWER LED, NORMALLY ON WHEN UNIT IS POWERED

  6

RED FIRE RELAY LEDS, NORMALLY OFF (RELAY UN-ENERGIZED)—BLINK WHEN RELAY ENERGIZED—ON (STEADY) WHEN RELAY 

DE-ENERGIZED

7

AMBER FAULT RELAY LED, NORMALLY OFF (RELAY ENERGIZED) BLINKS WHEN RELAY DE-ENERGIZED—ON (STEADY) WHEN 

RE-ENERGIZED (FAULT ACCEPT)

8A

TEST/FAULT ACCEPT BUTTON—IN NORMAL MODE, RE-ENERGIZES FAULT RELAY—IN TEST MODE, ACTIVATES RELAY DRIVE CIRCUITRY 

IN TEST MODE

8B

TEST BUTTON—ACTIVATES RELAY DRIVE CIRCUITRY IN TEST MODE

9

AMBER INHIBIT LED, NORMALLY OFF—ON TO INDICATE RELAYS ARE INHIBITED

10

LAMP TEST BUTTON—TESTS ALL LEDS AND DIGITAL DISPLAY

 11

KEYLOCK SWITCH—SELECTS NORMAL, RESET, TEST MODES

5

4

3

2A

1

3

2B

6

8B

9

10

11

10

11

5

9

7

6

8A

4

RELAY MODULE

1

3

5

2

4

6

RELAYS

RELAY

RELAY STATUS

ACCEPT

ALARM

FAULT

SELECT

TEST

SYSTEM

STATUS

FAULT

INHIBIT

POWER

LAMP

TEST

NORMAL

RESET

TEST

R6006A, C

RELAY MODULE

1

3

5

7

2

4

6

8

RELAYS

SELECT

TEST

SYSTEM

STATUS

FAULT

INHIBIT

POWER

LAMP

TEST

NORMAL

RESET

TEST

R6006B, D

STATUS

RELAY

B266

Figure 3—R6006 Relay Output Module Front Panel

Содержание Det-Tronics FDRS

Страница 1: ...elay and detonation output devices into a single system Figure 5 In addition to the Det Tronics flame detectors the FDRS accepts inputs from devices such as heat and smoke sensors and manual trip stations The FDRS provides alarm and fault relay outputs a detonator output that provides high speed output for direct connection to a deluge valve and extinguishing agent release signals for connection t...

Страница 2: ...hen used as a field replacement all operating features of the current controller are retained in addition to gaining the advanced features of the X Series detector In typical applications the four wire X Series detector can utilize all existing system wiring X Series Flame Detectors include the following X3301 Multispectrum IR Detector See Figure 1A X2200 UV Detector See Figure 1B X9800 IR Detecto...

Страница 3: ...d provides a digital display of system status using a numerical code Other features include individual zone identification and voting capability as well as manual oi testing See Figure 2 Voting of 2 or more UV flame detectors is required for compliance to ANSI NFPA 72 to maintain ground fault monitoring integrity R7494 Controller The R7494 Controller is also used with all X Series Pulse Output Fla...

Страница 4: ...T MODE 3 DIGITAL DISPLAY NORMALLY OFF TURNS ON TO INDICATE STATUS CHANGE AND RELAY AFFECTED 4 AMBER SYSTEM FAULT LED NORMALLY OFF ON TO INDICATE SYSTEM FAULT 5 GREEN POWER LED NORMALLY ON WHEN UNIT IS POWERED 6 RED FIRE RELAY LEDS NORMALLY OFF RELAY UN ENERGIZED BLINK WHEN RELAY ENERGIZED ON STEADY WHEN RELAY DE ENERGIZED 7 AMBER FAULT RELAY LED NORMALLY OFF RELAY ENERGIZED BLINKS WHEN RELAY DE EN...

Страница 5: ...ack of the BFD Mounting Rack The R7404 R7494 R6006 and R1425 Modules fit into a mounting rack which is located within the system enclosure Two mounting rack types are available Q4004 Universal Mounting Cage standard rack holds all system modules up to six Q1020 Wall Mount Metal Enclosure standard rack inside IP55 rated enclosure provides added protection System Enclosure An enclosure is provided t...

Страница 6: ...in the field Installation of the Flame Detection Releasing System involves 1 Mounting the enclosure that contains the prewired system mounting dimensions are included in the System Drawings Enclosure Mechanical Layout sheet 2 Installing and wiring the detector system wiring details are included in the System Drawings Detector Field Wiring sheet Refer to the appropriate Instruction Manual for detai...

Страница 7: ...l Solenoid Load Valve Coil Total Signaling Load Total Alarm Current for System in Amperes Table 3 Alarm Current Requirements at 24 vdc Device Type No of Devices x Standby Current Total Current for Device Type X2200 x 0 104 X9800 x 0 087 X5200 x 0 116 X3301 x 0 167 R7404A B x 0 062 R7494 x 0 063 R6006 x 0 104 R1425 x 0 104 W2400 x 0 015 BFD x 0 160 Resistor Network Load x 0 012 Heat Sensor x Manual...

Страница 8: ... R1425 Removal Replacement The R7404 R7494 R6006 and R1425 are not designed to be repaired in the field however field replacement can be accomplished by following the instructions below If a problem should develop first carefully check for proper wiring and switch settings If it is determined that the problem is caused by a defect in the module the device must be returned to the factory for repair...

Страница 9: ... can be assigned A written statement describing the malfunction must accompany the returned device or component to expedite finding the cause of the failure thereby reducing the time and cost of the repair Pack the controller circuit boards using sufficient packing material in addition to an anti static bag or aluminum backed cardboard as protection from antistatic discharge Return all equipment t...

Страница 10: ...NG DATE DATE ANGLE 1 0 0 0 00 0 00 0 000 01 005 CHECKED DRAWN REV DATE DATE ECO NO TOLERANCES ARE DESCRIPTION DETECTOR ELECTRONICS CORP 0 5 SIZE SCALE DRAWING NO MINNEAPOLIS MINNESOTA 55438 0 25 0 13 REV APPROVED DATE BATTERY FAILURE DETR CLARIFY 6458 C X9800 IR FLAME DETECTOR 007399 001 OR FAILURE RELAY BATTERY FAILURE DETECTOR ANSI NFPA 72 1999 CL 1 5 8 X2200 UV FLAME DETECTOR BFD 3 3 4 4 3 MODE...

Страница 11: ...9 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 J2 J1 CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 6...

Отзывы: