background image

1.3

95-8574

10

DETECTION/RELEASING SYSTEM "FM"

CADDS NAME: 6838-01d

A/B

006838-001

DWG, DESIGN REFERENCE FLAME

1 OF 

1

NEW RELEASE

8/24/01

CDS

5889-

2

NTS

D

1. FM APPROVED DRAWING - NO MODIFICATIONS PERMITTED WITHOUT REFERENCE TO FM APPROVALS.

X5200 UVIR FLAME DETECTOR

FDRS-FM-PE

INPUT TO R7404B CONTROLLER (X5200 PULSE OUTPUT):

AC POWER

(REF MANUAL)

FLAME DETECTION/RELEASING SYSTEM (FDRS)

INCLUDES:

R7404/R7494 CONTROLLER (QTY 4 MAX)

TERMINAL STRIP

Q4004 MOUNTING RACK

APPROVED FOR USE WITH THE FOLLOWING SOLENOID VALVES:

(ANSI/NFPA 72-1999)

OF EXTINGUISHING SYSTEM PANEL.

BATTERY BACK-UP

90 HOUR BATTERY

(REFERENCE MANUAL FOR

WET CELL BATTERY TYPES MUST BE WITHIN VENTED ENCLOSURES.

SEALED BATTERY TYPES DO NOT REQUIRE VENTED ENCLOSURES.

R6006 RELAY MODULE (QTY 1 MAX)

R1425 DETONATOR MODULE (QTY 1 MAX)

INPUT TO R1425 DETONATOR MODULE

INTENDED FOR USE WITH COMPATIBLE

FM APPROVED DEVICES (e.g. KIDDE DUAL SPECTRUM PM-5MPX)

BACK-UP CALCULATIONS)

MODEL A12(A36)-10A-24V-A1

BATTERY CHARGER

LaMARCHE POWER SUPPLY 

/

RELEASING/DELUGE

CIRCUITS PER NFPA 72

20VDC MIN.

CONTACT RATING: 12 AMPS PEAK (10mSEC), 

THE PRIMARY & SECONDARY POWER SUPPLY EQUIPMENT & CONTROLLERS MUST BE LOCATED 

 

WITHIN 20ft (6M) OF THE FLAME DETECTION/RELEASING SYSTEM WHERE THE CONDUCTORS ARE

INSTALLED IN CONDUIT OR EQUIVALENTLY PROTECTED AGAINST MECHANICAL DAMAGE.

3

2. DESIGN REFERENCE DRAWINGS:

X2200 UV FLAME DETECTOR: 007399-001

Q4004 MOUNTING RACK: 006843-001

R7404/R7494 CONTROLLER: 006840-001

R6006 RELAY MODULE: 006841-001

R1425 DETONATOR MODULE: 006842-001

DELUGE:

RELEASING:

SUITABLE FOR INTENDED USE

R1425 OUTPUT SPECIFICATIONS 

FAILURE RELAY

AC POWER

W2400 GRUND FAULT MONITOR MODULE (QTY 1 MAX)

W2400 GROUND FAULT MONITOR MODULE: 006848-001

LOW/HIGH DC VOLTAGE ALARM FAILURE RELAY

FLAME DETECTOR "B" LEAD & "D" LEAD CIRCUIT CONFIGURATION:

SPRINKLER SYSTEM OR AUTOMATIC RELEASE

FM APPROVED

AUTOMATIC RELEASE OF PREACTION & DELUGE

DWG NO

SH

REV

8

D

C

B

A

D

C

B

A

8

7

7

6

6

5

5

4

4

3

3

2

1

1

D

THEREOF IS EXPRESSLY PROHIBITED WITHOUT THE WRITTEN

UNLESS OTHERWISE SPECIFIED

DIMENSION          TOLERANCE

INCH    (MM)      INCH    (MM)

REMOVE ALL BURRS  BREAK ALL

EDGES AND SHARP CORNERS

THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY

INFORMATION AND ANY REPRODUCTION DISCLOSURE OR USE 

PERMISSION OF DETECTOR ELECTRONICS CORPORATION.

0.0

(0)

±

.0

2

FIRST USED ON

BILL OF MAT'L REQ.

TITLE

SHEE

T

APP'

D

APP'

D

DO NOT SCALE DRAWING

DATE

DATE

ANGLE 

±

1'

(0.0

)

(0.00)

0.00

0.000

 

±

.0

1

±

.005

CHECKE

D

DRAWN

REV

DATE

DAT

E

ECO NO

.

TOLERANCES ARE 

:

DESCRIPTION

DETECTOR ELECTRONICS CORP

.

±

(0.5)

SIZE

SCALE

DRAWING NO

.

MINNEAPOLIS, MINNESOTA 5543

8

±

(0.25)

±

(0.13

)

REV

APPROVE

D

DATE

BATTERY FAILURE DETR. CLARIFY

6458

C

X9800 IR FLAME DETECTOR: 007399-001

OR

FAILURE

RELAY

BATTERY FAILURE DETECTOR

ANSI/NFPA 72: 1999, CL 1-5.8

X2200 UV FLAME DETECTOR

(BFD)

3

3

4

4

3

MODEL M-4193-24G

MULTITEL

SUPERVISORY POWER ALARM/TROUBLE

SIGNALS TO PANEL FOR NOTIFICATION

9/5/97

MWM

OPTIONAL SUPERVISORY BATT. MONITOR.

DIV 2, GRP A,B,C,D (T3C);

DIV 1, GRP E,F,G; CL III;

DIV 2, GRP F&G (T3C). NEMA/TYPE 4X

DIV 1, GRP B,C,D;

CL I,

CL II,

CL I,

CL II,

X3301 IR FLAME DETECTOR

CL II/III DIV.2 GRP F & G (T3)

CL I DIV.2 GRP A,B,C & D (T3)

CL II/III DIV.1 GRP E,F & G (T5)

CL I DIV.1 GRP B,C & D (T5)

NEMA/TYPE 4X

(QTY 8 MAX PER CONTROLLER)

INPUT TO R7404B CONTROLLER (X9800 PULSE OUTPUT):

INPUT TO R7404B CONTROLLER (X3301 PULSE OUTPUT):

X5200 UVIR FLAME DETECTOR: 007399-001

X3301 IR FLAME DETECTOR: 007264-001

MODEL A36-30A-24V-ABD1

OR

MODEL A36-75A-24V-ABD1

OUTPUT FROM: 

R1425

R6006

OUTPUT FROM: 

4 AMPS CONTINUOUS

FOR SOLENOID OR SQUIB:

DC SOLENOID RATING: 4 AMPS @ 50VDC MAX., 

5

ADD 30A & 75A POWER SUPPLY,  C7051, X3300, X3301, 

&

5

5

5

5

EXPLOSIONPROOF FOR USE IN

EXPLOSIONPROOF FOR USE IN

R1 & R2 RESISTOR DIVIDER NETWORK, 10KOHM, 1/2W, 5% EACH.

6

6

R1

R2

POWER SUPPLY

CIRCUITS PER

SUPERVISORY

ELECTRONIC CURRENT

SIGNAL

PER NFPA 72

PER NFPA 72

CIRCUITS PER

POWER SUPPLY

ENCLOSURE MUST BE

ALARM/TROUBLE

1/4/02

CDS

7133

D

NEMA/TYPE 4X

CL II/III DIV.1 GRP E,F & G (T5)

CL I DIV.1 GRP B,C & D (T5)

CL II/III DIV.2 GRP F & G (T3)

CL I DIV.2 GRP A,B,C & D (T3)

EXPLOSIONPROOF FOR USE IN

NEMA/TYPE 4X

CL II/III DIV.1 GRP E,F & G (T5)

CL I DIV.1 GRP B,C & D (T5)

CL II/III DIV.2 GRP F & G (T3)

CL I DIV.2 GRP A,B,C & D (T3)

EXPLOSIONPROOF FOR USE IN

SINGLE DETECTOR CONFIGURATION: EQUIVALENT TO ANSI/NFPA 72 CLASS B, STYLE A INITIATING DEVICE CIRCUIT (IDC).

REDUNDANT DETECTOR CONFIGURATION: EQUIVALENT TO ANSI/NFPA 72 CLASS A, STYLE D INITIATING DEVICE CIRCUIT (IDC).

X9800 IR FLAME DETECTOR 

(QTY 8 MAX PER CONTROLLER)

(QTY 8 MAX PER CONTROLLER)

(QTY 8 MAX PER CONTROLLER)

GROUP E: SKINNER 73218BN4UNLVNOC111C2,

REMOVE X3300 & C7050/7051. ADD

NFP DETECTORS. UPDATE NOTE 5.

INPUT TO R7404B CONTROLLER (X2200 PULSE OUTPUT):

ANSI/NFPA 72: 1999, CL 1-5.8

ANSI/NFPA 72: 1999, CL 1-5.8

ANSI/NFPA 72: 1999, CL 1-5.8

INITIATING DEVICE CIRCUITS (IDC)

CLASS A, STYLE D PER ANSI/NFPA 72

CLASS A, STYLE D PER ANSI/NFPA 72

INITIATING DEVICE CIRCUITS (IDC)

 24VDC, 10W, 5/8" ORIFICE, 5-175 P.S.I.

F

ig

ur

e 5

F

la

m

e D

et

ec

tio

n

/R

el

ea

si

ng S

ys

te

m – B

lo

ck D

ia

gr

am

Содержание Det-Tronics FDRS

Страница 1: ...elay and detonation output devices into a single system Figure 5 In addition to the Det Tronics flame detectors the FDRS accepts inputs from devices such as heat and smoke sensors and manual trip stations The FDRS provides alarm and fault relay outputs a detonator output that provides high speed output for direct connection to a deluge valve and extinguishing agent release signals for connection t...

Страница 2: ...hen used as a field replacement all operating features of the current controller are retained in addition to gaining the advanced features of the X Series detector In typical applications the four wire X Series detector can utilize all existing system wiring X Series Flame Detectors include the following X3301 Multispectrum IR Detector See Figure 1A X2200 UV Detector See Figure 1B X9800 IR Detecto...

Страница 3: ...d provides a digital display of system status using a numerical code Other features include individual zone identification and voting capability as well as manual oi testing See Figure 2 Voting of 2 or more UV flame detectors is required for compliance to ANSI NFPA 72 to maintain ground fault monitoring integrity R7494 Controller The R7494 Controller is also used with all X Series Pulse Output Fla...

Страница 4: ...T MODE 3 DIGITAL DISPLAY NORMALLY OFF TURNS ON TO INDICATE STATUS CHANGE AND RELAY AFFECTED 4 AMBER SYSTEM FAULT LED NORMALLY OFF ON TO INDICATE SYSTEM FAULT 5 GREEN POWER LED NORMALLY ON WHEN UNIT IS POWERED 6 RED FIRE RELAY LEDS NORMALLY OFF RELAY UN ENERGIZED BLINK WHEN RELAY ENERGIZED ON STEADY WHEN RELAY DE ENERGIZED 7 AMBER FAULT RELAY LED NORMALLY OFF RELAY ENERGIZED BLINKS WHEN RELAY DE EN...

Страница 5: ...ack of the BFD Mounting Rack The R7404 R7494 R6006 and R1425 Modules fit into a mounting rack which is located within the system enclosure Two mounting rack types are available Q4004 Universal Mounting Cage standard rack holds all system modules up to six Q1020 Wall Mount Metal Enclosure standard rack inside IP55 rated enclosure provides added protection System Enclosure An enclosure is provided t...

Страница 6: ...in the field Installation of the Flame Detection Releasing System involves 1 Mounting the enclosure that contains the prewired system mounting dimensions are included in the System Drawings Enclosure Mechanical Layout sheet 2 Installing and wiring the detector system wiring details are included in the System Drawings Detector Field Wiring sheet Refer to the appropriate Instruction Manual for detai...

Страница 7: ...l Solenoid Load Valve Coil Total Signaling Load Total Alarm Current for System in Amperes Table 3 Alarm Current Requirements at 24 vdc Device Type No of Devices x Standby Current Total Current for Device Type X2200 x 0 104 X9800 x 0 087 X5200 x 0 116 X3301 x 0 167 R7404A B x 0 062 R7494 x 0 063 R6006 x 0 104 R1425 x 0 104 W2400 x 0 015 BFD x 0 160 Resistor Network Load x 0 012 Heat Sensor x Manual...

Страница 8: ... R1425 Removal Replacement The R7404 R7494 R6006 and R1425 are not designed to be repaired in the field however field replacement can be accomplished by following the instructions below If a problem should develop first carefully check for proper wiring and switch settings If it is determined that the problem is caused by a defect in the module the device must be returned to the factory for repair...

Страница 9: ... can be assigned A written statement describing the malfunction must accompany the returned device or component to expedite finding the cause of the failure thereby reducing the time and cost of the repair Pack the controller circuit boards using sufficient packing material in addition to an anti static bag or aluminum backed cardboard as protection from antistatic discharge Return all equipment t...

Страница 10: ...NG DATE DATE ANGLE 1 0 0 0 00 0 00 0 000 01 005 CHECKED DRAWN REV DATE DATE ECO NO TOLERANCES ARE DESCRIPTION DETECTOR ELECTRONICS CORP 0 5 SIZE SCALE DRAWING NO MINNEAPOLIS MINNESOTA 55438 0 25 0 13 REV APPROVED DATE BATTERY FAILURE DETR CLARIFY 6458 C X9800 IR FLAME DETECTOR 007399 001 OR FAILURE RELAY BATTERY FAILURE DETECTOR ANSI NFPA 72 1999 CL 1 5 8 X2200 UV FLAME DETECTOR BFD 3 3 4 4 3 MODE...

Страница 11: ...9 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 J2 J1 CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 6...

Отзывы: