1.3
95-8574
2
SySTEm POwER aND wIRINg
The R7404, R7494, R6006, R1425 and W2400 are all
mounted within a mounting rack that is located within a
NEMA Rated enclosure. System interconnection within
the enclosure is completed as shown on the System
Drawings. (Figure 6 identifies external circuit wiring).
A terminal strip is provided for field wiring. The power
supply/battery charger and backup batteries convert
120 vac supply voltage to +24 vdc to power the system.
Refer to the System Drawings for wiring details of the
specific system.
MAJOR COMPONENT DESCRIPTIONS
X-Series Flame Detectors with pulse/relay output
are designed for use in controller based systems. In
addition to use in new systems, they can serve as a
direct field replacement for Det-Tronics controller
based flame detectors that generate a pulse output (not
compatible with R7484 and R7409B/C).
When used as a field replacement, all operating features
of the current controller are retained in addition to
gaining the advanced features of the X-Series detector.
In typical applications, the four wire X-Series detector
can utilize all existing system wiring.
X Series Flame Detectors include the following:
X3301 Multispectrum IR Detector — See Figure 1A.
X2200 UV Detector — See Figure 1B.
X9800 IR Detector — See Figure 1C.
X5200 UV/IR Detector — See Figure 1D.
COmmON x-SERIES ChaRaCTERISTICS
The X-Series detector has Division and Zone explosion-
proof ratings and is suitable for use in indoor and
outdoor applications. The housing is available in
copper-free aluminum or stainless steel, with NEMA 4X
and IP66 rating.
Outputs
The detector is furnished with fire and fault relays. The
relays are rated 5 amperes at 30 VDC.
A tricolor LED on the detector faceplate indicates
normal, fire alarm and fault conditions.
Figure 1A—X3301 Multispectrum IR Flame Detector
Figrue 1B—X2200 UV Flame Detector
Figure 1C—X9800 IR Flame Detector
Figure 1D—X5200 UV/IR Flame Detector