4.1
WIRING PROCEDURE
IMPORTANT
Do not apply power until the wiring procedure is
complete and has been verified.
1. Locate the sensor where it will be accessible for
maintenance. Excessive heat or vibration can
result in premature failure of any electronic device
and should be avoided if possible.
2. The junction box should be electrically connected
to earth ground.
3. Figure 8 shows typical wiring for stand alone
operation. Figure 9 shows typical wiring for
PIRVOL with Det-Tronics supplied junction box.
Figure 10 shows the wiring terminals located
inside the junction box. The PIRVOL wiring color
code is:
Red lead
= +24 volts dc
Black lead = – (common)
White lead = 4 to 20 ma signal output
Yellow lead* = Calibration input
Green lead = Chassis ground
* If the calibration wire (yellow lead) is not
being used, do not connect this wire to
ground. Trim excess length and insulate wire
so no shorting can occur.
7
95-8522
Figure 6—Tall PIRVOL Junction Box with Window
Figure 7—Short PIRVOL Junction Box
Figure 9—Typical PIRVOL Wiring,
with Det-Tronics Junction Box
DET-TRONICS JUNCTION BOX
B1756
PIRVOL
DETECTOR
GREEN
YELLOW
WHITE
BLACK
RED
SPARE
CAL
4 – 20
RET
+
24
CHASSIS
CAL
4 – 20
RET
+
24
+
24 Vdc
4-20 mA IN
–
+
Figure 8—Typical PIRVOL Wiring, Stand Alone Configuration
–
RED
BLaCK
WhITE
yELLOW
GREEN
4 TO 20 MILLIaMPERES
PIRVOL
+
A2031
NOTES: CaLIBRaTION PUShBUTTON, CURRENT METER
aND POWER SUPPLy aRE NOT SUPPLIED.
CaLIBRaTE SWITCh ShOWN INSTaLLED, hOWEVER,
FIELD CaLIBRaTION IS NOT REqUIRED UNDER
NORMaL CIRCUMSTaNCES.
+
24 VDC
POWER SUPPLy
–
+
CaLIBRaTE