4.1
5
95-8522
SIGNaL DISPLay DEVICE
If a local or remote digital display for indication
of detected gas concentration is required, it is
recommended to utilize a scalable display device
with a clearly marked unit of measurement in % by
volume. Under no circumstances should a %LFL unit
of measure display module be used to display the
PIRVOL signal output.
OPERaTING MODES
Warmup
When power is applied to the PIRVOL, it enters a
Warmup mode (for approximately one minute) in which
it performs diagnostic checks and allows the sensors
to stabilize before beginning normal operation. The
current output during this period is 0 milliamperes. At
the end of the warmup period with no faults present,
the PIRVOL automatically enters the Normal operating
mode. If a fault is present after the warmup, the
current output will indicate a fault.