background image

21 

 

of the boiler (Picture 5.1, pos. 22). Boiler fume pipes must be cleaned by opening the upper boiler 
door and removing smoke spins. The boiler heating surfaces are recommended to clean as often 
as  possible,  since  clean  heating  surfaces  increase  boiler  efficiency.  Deposits  or  soot  layer  on  the 
surface cannot be thicker than 3 mm. 
When cleaning the 2

nd

 stage fume pipes, soot deposits from a boiler flue pipe must be removed 

every  time  upon  cleaning  the  boiler  funnels.  Ash  and  soot  must  be  removed  through  a  special 
opening, closed with a lid on the side of the flue pipe (Picture 5.1, pos.10). 
 
 

8. REQUIREMENTS FOR SAFE OPERATION 

 
8.1. The following safety requirements must be applied to water heating boilers UT - 100, UT - 150, 
UT-200, UT-250, UT-320 UAB UT boilers, manufactured by CJSC “UT KATILAI“. For the purpose, it is  
required to use the below listed organizational and technical measures. 
8.2. Organizational Measures 
After installation works, an owner of a boiler (boilers) must ensure that: 

-

 

a boiler (boilers) is (are) included to the company's list of potentially dangerous equipment 
and specify its number in the boiler certificate; 

-

 

a  responsible  person  for  boilers  (boilers)  maintenance  has  been  assigned,  by  recording 
his/her data in the boiler certificate; 

-

 

the first inspection after the installation has to be performed at the presence of an expert of 
any republic (having a relevant permission) public authority. the inspection results must be 
recorded in the boiler certificate; 

-

 

the boiler certificate must be completely filled in; 

-

 

boiler  servicing  must  be  administered  by  persons  not  younger  than  18  years  old,  having 
passed  the  compulsory  operational  safety  briefings,  and  their  knowledge  on  fire  safety, 
operational and safety at work has been checked. 

-

 

during  operation,  an  owner  of  a  boiler  (boilers)  must  ensure  boiler  technical  maintenance 
inspections  in  due  time  (see  section  9  of  these  instructions)  to  follow  technical  safety 
measures, controls, and timely instrumentation verification listed in clause 3.8; 

-

 

a boiler-station, as a power facility, must be recognised by the State Energy Inspectorate as 
suitable for use. 

 

Boilers'  operating  personnel  must  ensure  an  order  in  boiler-station  rooms  and  around  the 

outside  facilities,  that  is,  not  to  block  passages,  not  to  store  unnecessary  items  in  the  boiler-
station,  not  to  overload  flue  pipes  with  flammable  items,  not  to  store  combustible  or  explosive 
materials in the boiler-station, to clean the boiler-station and its installations on a regular basis. 
 

By  controlling  and  by  using  instrumentation,  by  paying  attention  to  certain  external  signs 

(water leakage outside the piping or fittings; smoking through collars from the boiler or flue pipes; 
the  emergence  of  unusual  sounds:  water  bubbling,  rattle,  squeak  of  rolling  bearings,  etc.), 
evidencing an abnormal functioning of heating systems, boiler (boilers) operating personnel must 
constantly control a boiler’s (boilers’) parameters and sizes and technical condition of the overall 
boiler-station  equipment.  All  boiler  equipment  malfunctions,  occurred  during  a  shift,  must  be 
recorded  in  a  logbook.  Apart  from  these  malfunctions,  the  logbook  must  be  used  to  record 
equipment  shutdowns,  boiler  cleansing,  performed  during  the  shift,  details  of  the  operating 
personnel, and if required, work schedules and assignments. 

Содержание UT-100

Страница 1: ...1 WATER HEATING BOILERS UT 100 UT 150 UT 200 UT 250 UT 320 USER INSTRUCTIONS ...

Страница 2: ...VISIONS 3 3 TECHNICAL DATA 4 4 SCOPE OF SUPPLY 5 5 DESIGN 6 6 INSTALLATION 9 7 USE OF BOILER 19 8 REQUIREMENTS FOR SAFE OPERATION 21 9 MAINTENANCE AND INSPECTIONS 23 10 STORAGE AND TRANSPORTATION 24 11 WARRANTY STATEMENT 25 DECLARATION OF CONFORMITY 26 ...

Страница 3: ...which are equipped with central heating systems for the purposes of heating for domestic or other process hot water treatment through intermediate water preheaters 2 2 Heating and hot water treatment systems connected to the boilers must apply only softened water according to LST EN 12953 10 requirements 2 3 The boilers are intended to burn lump solid fuel firewood wood waste non bulky wood waste ...

Страница 4: ...er water capacity maximum l 342 469 616 683 1065 Boiler heating surface m2 7 6 11 4 14 7 17 7 25 8 Safety device pressure bar 4 0 Pressure outside boiler Pa 28 34 40 46 58 Temperature of combustion gas o C 250 Boiler water circulation forced Type of fuel Lump solid with add on combustion chamber bulky wood waste sawdust chips Furnace depth max firewood length mm 948 800 1148 1100 1348 1300 1546 14...

Страница 5: ...bar Ø 160 mm 1 1 1 1 1 6 Three way valve for pressure gauge Dn 15 1 1 1 1 1 7 Thermal pressure gauge 0 120 o C 1 1 1 1 1 8 Fan CMP 512 2M 1 1 9 Fan CMP 514 2M 1 1 10 Fan CMP 616 2M 1 11 Control console temperature sensors comp 1 1 1 1 1 12 Fire grates x 13 Cleaning toolkit 1 1 1 1 1 14 Tech documentation set 1 1 1 1 1 Boiler No is supplied with UT a set of water heating boiler according to the lis...

Страница 6: ... pos 9 through a flue pipe pos 6 which is provided with a traction control valve pos 8 For cleaning a soot or ash deposit this interim flue pipe is provided with a manhole closed with a lid pos 10th 5 5 The entire outer surface of the boiler is insulated with 50 mm heat insulation layer pos 29 from the outside sealed with decorative coating pos 30 5 6 For boiler incoming flow temperature and press...

Страница 7: ...7 Picture 5 1 Design of water heating boilers UT 100 UT 150 UT 200 UT 250 UT 320 ...

Страница 8: ...hamber door screen shields pcs Door seal TC SPx2 20x20 mm Control console fuse 5A pcs 200x400 200x500 200x600 200x700 250x900 565x430 565x530 565x630 565x730 565x930 UT 100 5 1 2 x 2580 1 UT 150 6 1 2 x 2780 1 UT 200 7 1 2 x 2980 1 UT 250 7 1 2 x 3180 1 UT 320 7 1 2 x 3580 1 ...

Страница 9: ...f the boiler but not lower than 2 m in height on lower floors and basements of residential public except for premises specified in cl 6 2 2 and industrial buildings where the total boiler capacity does not exceed 1 000 l 6 2 2 Boilers are prohibited from installing immediately under the room where a lot of people may gather under theatre lobbies or audience halls sauna s dressing rooms and washing...

Страница 10: ... 1500 3000 2500 800 1500 800 c installation of multiple boilers each against other 800 800 1500 4000 800 1500 800 N a newly installed boiler house S a boiler house installed in old premises If the distance Fmin from the boilers front line to the wall is 3 000 mm the wall is permitted to be equipped with other boiler house equipment pumps water preheaters manifolds etc provided that the distance be...

Страница 11: ...s a recommended height of foundation Table 6 3 2 Type of boiler UT 100 UT 150 UT 200 UT 250 UT 320 Length mm 1100 1300 1500 1500 1700 Width mm 600 700 800 900 1100 Boilers can be installed only on a non combustible floor 6 3 1 Connection Dimensions Layout of all boiler junction pipes their purpose and connection dimensions are provided in Picture 6 3 3 and Picture 5 1 Ceiling Boiler Floor ...

Страница 12: ... 200 1950 1770 1363 321 1600 1090 330 150 100 300 DN50 11 2 1 UT 150 830 690 180 240 1950 1770 1363 321 1830 1290 457 180 100 330 DN80 11 2 1 UT 200 930 790 200 280 1950 1770 1363 321 2060 1490 650 180 100 330 DN80 11 2 1 UT 250 1030 890 220 3200 1950 1770 1363 321 2060 1490 650 190 100 340 DN100 11 2 1 UT 320 1250 1110 240 400 2160 1980 1563 321 2360 1700 650 210 150 420 DN100 2 11 4 ...

Страница 13: ...ocated in areas of potential air accumulation and jams that block water circulation We recommend a vent assembly diagram shown in Picture 6 4 1 Picture 6 4 1 Vent Assembly Diagram 1 automatic air vent device 2 valve tap Automatic air vent is used to remove air accumulating during the operation A valve or tap is used to remove air pockets by filling a pipeline with water 6 4 4 Pictures 6 4 3 and 6 ...

Страница 14: ...50 UT 200 UT 250 UT 320 6 4 0 10 10 6 6 Flue Pipe Connection 6 6 1 A cross section of flue pipes connected to the boiler cannot be smaller than a cross section of the outgoing boiler flue pipe see Table 6 6 1 Table 6 6 1 Type of boiler UT 100 UT 150 UT 200 UT 250 UT 320 Cross section cm2 600 726 850 980 1227 6 6 2 A flue pipe must be fitted with elevation at least 10 from the boiler to the chimney...

Страница 15: ...system with hot water treatment when temperature of return water in the heating system and boilers is controlled by means of a four way mixing valve Hot water treatment To the heating system Hot water boiler Hot water boiler System replenishment To the drain networks To the drain networks ...

Страница 16: ...system with hot water treatment when temperature of return water in the heating system and boilers is controlled by means of a three way mixing valve Hot water treatment To the heating system Hot water boiler Hot water boiler To the drain networks To the drain networks System replenishment ...

Страница 17: ... maintenance in boiler circuit 15 Filter Solids collection 16 Three way four way valve Flow separation or mixing 17 Tap valve Compensatory loop closing with a device against a reckless closure 18 Compensatory vessel Compensation of changes in water volume 19 Valve tap Hot water treatment pump service 20 Filer Solids collection 21 Pump Water flow maintenance in hot water treatment circuit 22 Non re...

Страница 18: ... other heating surface cleaning smoke soot ash or dust may release into the environment therefore it is necessary to provide and install an exhaust ventilation with a capture hood see Picture 6 8 by the boiler above the boiler cleaning and fuel loading doors 1 boiler 2 fan 3 air duct 4 capture hood 5 valve Picture 6 8 Local Boiler Ventilation Equipment Layout Combination of several boilers local e...

Страница 19: ...a fan see Picture 5 1 pos 32 When the fuel layer fan properly burns up turn the fan off open a combustion chamber door and load the main fuel throughout the grate area coarse wood peat or sawdust briquettes coal You can monitor the combustion process through a hole in the combustion chamber door see Picture 5 1 pos 23 This type of boiler is not a durable capacity boiler thus fuel must be loaded in...

Страница 20: ... the boiler water leaks through the welded seams upon loss of flue pipe thrust behind the boiler or upon failure of exhauster upon explosion in the furnace upon explosion or ignition of combustible debris in flue pipes or in gas cleaning facilities as well as other cases where employees or equipment are at risk upon loss of voltage in remote and automatic control or measurement devices 7 6 1 When ...

Страница 21: ... be administered by persons not younger than 18 years old having passed the compulsory operational safety briefings and their knowledge on fire safety operational and safety at work has been checked during operation an owner of a boiler boilers must ensure boiler technical maintenance inspections in due time see section 9 of these instructions to follow technical safety measures controls and timel...

Страница 22: ...erating Boiler control console temperature sensor closing or adjusting valves pressure safety devices only provided in the boiler design or supplied with the boiler with the parameter values no lower or no higher than operating ones specified the boiler certificate During operation a short term increase in pressure above the specified one in the boiler certificate by maximum 10 is allowed A casing...

Страница 23: ... per year 9 2 5 Internal inspection after each cleaning and repair 9 3 Before the internal inspection and hydrostatic testing a boiler must be cooled down and disconnected with valves from the heating surfaces dirt soot and ash must be thoroughly removed When carrying out an internal and external inspection please pay attention to the state of boiler walls both inside and outside funnels and welde...

Страница 24: ...tened Control instrumentation fittings pressure limiting devices safety valves a fan supplied with the boiler must be stored in a room at a temperature of at least 5 C 10 2 Do not load boilers on top of each other during their storage and transportation 10 3 The upper part of the boiler is fitted with two lifting loops for boiler loading or unloading Boiler can be unloaded or loaded with an automa...

Страница 25: ...able 5 1 see Section 5 11 3 A boiler buyer owner must demand of timely making the records above said in this Section on the boiler type and number dates of sale and installation since otherwise the manufacturer s warranty statement under clause 11 1 shall not be applicable to the boiler Date of sale th 201__ L S ______________________________________________________ manufacturer s responsible pers...

Страница 26: ...temperature up to 95o C Fuels solid fuel We hereby declare that a hot water boiler UT serial No year of manufacture 201 meets the requirements of installation project No technical documentation and the European Community Council s Pressure Equipment Directive 97 23 EC The declaration shall be invalid if the product design is modified without the consent of the manufacturer or upon non compliance w...

Отзывы: