EDGE-3
Soundproof MDC O&M
Page 10
Installation
The EMS provides supplementary protection via the fused inlet by 2 x High Rupture Capacity fuses rated T5AH250V.
The EDGE System for continued compliance must be provided with an appropriate Pre
-
approved power cord fitted with a regional
plug to a maximum of 3 metres in length.
The power cord specification is defined below:
Type SJT or SVT / HO5VV
-
F <HAR., 3 x 18 AWG (1.0mm), 2C +PE rated 300V, VW
-
1 terminated with an IEC 60320
-
1 C13
appliance coupler and a regional plug.
The EDGE may be connected for permanent installation via a dedicated power source in accordance with local and regional electri-
cal codes via an appropriately rated Isolator of which should be accessible and no more than 2 metres away from the EDGE Cabi-
net once installed
The EDGE power cable is to be installed via the cable entries fitted to the EDGE cabinet. Any Power cables to be provided to the
EDGE cabinet both internally and externally, are to be routed to avoid damage and risk of further hazards.
Isolating of EDGE System
Turn off the power to the EMS and Fans by selecting the switch shown left to the off position (currently
showing as
‘
on
’
in the picture).
Turn off input power at source and remove the IEC Input connector to the EMS.
INTERNAL EQUIPMENT
Any electrical equipment to be installed within the EDGE System is to be suitably electrically protected, again consideration to
power cable installation and routing both internally and externally is a must.
If electrical distribution blocks are to be used they should not be overloaded, and the ampacity should not exceed the rated capaci-
ty of the distribution block.
Consideration for isolating equipment to be installed within the EDGE Cabinet should also be made.
If rack sliders are used high up in the cabinet ensure that there is sufficient weight at the bottom of the cabinet to support heavy
equipment to avoid the cabinet tipping. We recommend heavy equipment mount as low as possible.