EDGE-3 

Soundproof Micro Data Center

 

We 

engineer 

for a sustainable tomorrow.

 

O&M Manual

 

Содержание EDGE-3

Страница 1: ...EDGE 3 Soundproof Micro Data Center We engineer for a sustainable tomorrow O M Manual ...

Страница 2: ... OR ANY PARENT AFFILIATE OR SUBSIDIARY COMPANY OF USYSTEMS LTD OR THEIR RESPECTIVE OFFICERS DIRECTORS OR EMPLOYEES BE LIABLE FOR ANY DIRECT INDIRECT CONSEQUENTIAL PUNITIVE SPECIAL OR INCIDENTAL DAMAGES INCLUDING WITHOUT LIMITATION DAMAGES FOR LOSS OF BUSINESS CONTRACT REVENUE DATA INFORMATION OR BUSINESS INTERRUPTION RESULTING FROM ARISING OUT OR IN CONNECTION WITH THE USE OF OR INABILITY TO USE T...

Страница 3: ...t 14 15 Door removal Front 16 Door removal Rear 16 Fan panel removal 17 Cable entry system 18 Gland plates 19 Extension kit assembly 20 Plinth kit assembly 21 EDGE 3 DAX kit assembly 22 EDGE Management System Operation 23 Product Description 24 Quick starter guide 25 WebUI Overview 26 Dashboard 27 Fan Speed 28 Environmental 29 Security 30 Alerts 31 32 Reporting 33 36 Settings Network 37 Device Man...

Страница 4: ... damage Make sure that all parts are accounted for Report any damage immediately to the shipping agent Report missing contents damage or other problems immediately to USystems or your reseller Please Recycle The shipping materials are recyclable Save them for later use or dispose of them appropriately ...

Страница 5: ...o persons or appropriate lifting equipment to carry or manoeuvre Appropriate lifting and carrying instructions should be followed This Marking when used indicates that product is configured for 100 to 130V operation This Marking indicates that product is configured for 200 to 240V operation Safety Indicators The following are used throughout the documentation to indicate the appropriate hazard or ...

Страница 6: ...te and EMS marking for the voltage set to The EMS appliance outlets are for the EDGE fan power only DO NOT plug any other appliance into the EMS power Outlets When performing maintenance the EDGE System should be Isolated or the appropriate instructions followed When Installing equipment within the EDGE ensure additional safety Instructions are specified Power and distribution cables should be ins...

Страница 7: ...a b c d e Where a 3 Soundproofed variant 24 to 42U b Single alpha numeric character for colour finish Non safety critical c Height in U model dependant 24U to 60U d Depth dm 06 to 14 e Voltage Input Fan module 15 100 130V or 24 200 240V Example of Identification Rating label The example above shows an EDGE 3 Soundproof cabinet 24U in height 120cm depth configured for 240V input with two fan module...

Страница 8: ...binet with equipment inside place the heavy equipment at the lower part of the 19 inch area Maximum load on castors is 500kg Make sure the levelling feet are up and push the cabinet only from the front or rear when moving the cabinet on its castors Never push the cabinet from the sides to avoid potential tipping When installed ensure the adjustable feet are down and the cabinet is secured CAUTION ...

Страница 9: ...tage INPUT marking located on the rear panel of the EMS Rear panel of EMS showing Voltage configured for 200 240V Input Voltage range 100 130V 200 240V 50 60Hz 5A max Voltage input model dependant Fan Module Voltage Refer to EMS Rear panel model Identification rating for configuration WARNING The EDGE 3 equipment is configure for either 100 130V fans or 200 240V dependant on the fans fitted this w...

Страница 10: ...er cables to be provided to the EDGE cabinet both internally and externally are to be routed to avoid damage and risk of further hazards Isolating of EDGE System Turn off the power to the EMS and Fans by selecting the switch shown left to the off position currently showing as on in the picture Turn off input power at source and remove the IEC Input connector to the EMS INTERNAL EQUIPMENT Any elect...

Страница 11: ... location for your enclosure Ambient temperature in the room should be as low as possible to allow efficient cooling Do not install next to a radiator or heat source If installing with a DAX Direct Airflow eXhaust allow no more than 2m from a wall or window pan from the rear of the enclosure Do not place the enclosure in direct sunlight or in a small non air conditioned space Place the enclosure c...

Страница 12: ...ar and that all cabling should be kept managed against the infill panels provided using jumper rings or cable trunking The result of best practice sealing no hot air recirculation The second zone is the IT equip ment space and sealing between the first and second zone is critical the EDGE 3 cabinet comes as standard with foam infills which covers the periphery of the 19 area see Figs 2 and 4 Cabli...

Страница 13: ...s require no fixings and play an important role in both airflow and sound proof management A major benefit is the prevention of hot air re circulation which eliminates the risk of hot spots Keeping the vertical and horizontal cabling organised and managed is essential in order to allow ambient air to pass through onto the active equipment The foam running around the sides of the infills must be ma...

Страница 14: ...ng the mounting angles This task can only be performed when there is no IT equipment inside of the cabinet A Philips screwdriver and a 10mm spanner is needed to perform this task 1 Take off both side panels to gain access to the depth support rails by opening both front and rear doors turn the cam locks on the side panel to undo them from each depth support 2 Use a Philips screwdriver and 10mm spa...

Страница 15: ...top and bottom mounting angle supports by using the Philips screw driver and 10mm spanner 4 Move the mounting angle and infills into the desired place Screw the mounting angle back into the top and bottom mounting angle support and infills back into the 3 depth supports ...

Страница 16: ...disconnected Open both doors to 135 does not need to be exact to allow the most grip when holding onto the door and lift off both hinges Door removal Rear Active Fan side Please follow local safety protocols Advisory 2 people to remove this door Turn active door to a 135 position and unplug the IEC power connector and 6 way Molex as shown and lift the door of its hinges ...

Страница 17: ...l turn off power to the fans 1 Disconnect the IEC and fan connector cable from the fan panel 2 Using a Philips screwdriver unscrew the 9 screws surround ing the fan panel as shown 3 The fan panel will now slide out reverse the removal procedure to install the fan module ...

Страница 18: ...e gland plate by unscrewing the 2 m6 bolts and lifting the panel away from the enclo sure Keep somewhere safe if needing to put back Remove the yellow tape cover from the cable entry system foam Put cabling through and evenly distribute it along the cable entry system to allow for the best seal ing Keep the cable entry foam together and feed it through the gland hole and firmly press down on the s...

Страница 19: ... To remove the gland plate unscrew using a Philips head screw driver while holding onto the nut to avoid dropping if removing from the top frame Gland plates are put in tightly to create a seal so it can be stiff removing and place back in To ensure optimum running efficiency it is important that seal integrity is maintained by utilising either cable entry system page 18 or other forms of cable gr...

Страница 20: ...he performance of the cabinet 1 Remove the rear active doors following instructions on page 16 2 Remove original hinges on frame using allen key via relief in corners post rear of hinge 3 Fix 4x retainer brackets onto lid and base using m6 fixings 4 Fit extension unit using M6 fixings supplied into 4x retainer brackets lid and base 5 Attach the active doors and use the extensions cables provided t...

Страница 21: ...onding plinth corners left hand and right hand on each corner with the M6 bolt and nut and the M10 nut as per removal make sure the levelling foot is attached to the plinth corner before fitting it onto the UCoustic base Once each plinth corner is fitted proceed to fit the external plinth panels using the M6 x 25 bolt onto a tapped hole on the plinth corner Unwind the levelling feet till the casto...

Страница 22: ...12U EDGE 3 Remove the gland plate located at the top of the cabinet to the rear Keep the M6 fixings safe as these will be required later Stage 1 Stage 2 Locate ventilation interface to rear of cabinet lid lining up entry holes in both parts ensuring that the gasket seals against lid edges Refit gland plate re using M6 fixings Alternatively use the cable entry system which will also assist clamping...

Страница 23: ...Page 23 EDGE Management System EMS Product User Guide ...

Страница 24: ...o the dedicating incoming power source and Fan power distribution and control The EMS is a networkable environmental monitoring and security product This following is a list of ancillary devices currently available to install Temperature sensors up to 4 EC Fans up to 2 Contact sensors up to 6 Aisle containment door open close UTelligent Locking LCD Alarm Screen ...

Страница 25: ... screen will require boot up time and is communicating with the EDGE Management System via wi fi a delay of up to 5 minutes on boot up before communication has been established 5 In order to use the WebUI Web User Interface an Ethernet cable from the EDGE Management System to your network is needed Plug the Ethernet cable into the EDGE Management System RJ45 port and then to a live network port on...

Страница 26: ...device there is a default Administrative account which to login to requires the following credentials Default username Admin Default password Admin12 case sensitive If unable to connect please contact the Network administrator to allow the use of this IP address or connect directly to the EDGE Management System via ethernet and adjust your IPv4 properties to match Once the EULA has been accepted i...

Страница 27: ...een Menu Left side of the dashboard is the menu with a list of different options these areas can be locked out for certain users please see page 20 for user accounts Cabinet Status Table Cabinet name By default it is named as EMS followed by 6 digits from the MAC address please see page 19 settings to change this It is also the hostname for the device Fan Status Displays the fan status and its val...

Страница 28: ...e rate at which the fans speed up per degree Celsius from the Base speed They will keep speeding up at this rate until they are running at 100 10V i e they are not capped They will hit 100 at a temperature dependant on the ramp rate set This does not require a restart it will change when selecting save the settings There will be 2 different set ramp rates which are listed in the table below and a ...

Страница 29: ...e changed either using the arrows provided or by manually entering it by selecting the text field in between the arrows Click on Environment in the left hand column select the on button Set the alarm temperature threshold to be notified of when temperature reaches the selected number To receive email alarms See page 19 to set up SMTP settings emails Click Save settings to set all changes ...

Страница 30: ...ra this is accessed from the toggle below the camera feed To adjust the image without having to open the doors the camera s can be activated using the Activate buttons Capture type will change weather a video or image is captured Settings can be saved or reset using the buttons Photographic Security Records To view the photos videos taken select the picture the default view will show 12 images per...

Страница 31: ...ay on your enclosure with change to Amber Service Alert USystems are able to provide your enclosure with a service when ever you need For more information on what is offered in a service please contact USystems To activate this option simple select the On button and click on the date to choice or type it in yourself then select save ...

Страница 32: ... that the enclosure is situated could result in the enclosure absorbing dust so it is recommended to each customer to use a filter to prevent your IT equipment from unwanted material in the air If your enclosure has a filter it is also recommend using this feature to notify alert when it may need cleaning or replacing To activate this option simple select the On button and click on the date to cho...

Страница 33: ...ded for up to 3 months This includes Fan fail access and temperature over threshold data reports of the data are available to download onto a csv spreadsheet The records may be displayed 10 25 50 or 100 per page Search by date and time using the same format from timedate column ...

Страница 34: ...he Temperature Log report is a list of temperature recorded up to 3 months Reports of the data are available to download onto an csv spreadsheet The records may be displayed 10 25 50 or 100 per page Search by date and time using the same format from timedate column ...

Страница 35: ...e Log report is a list of Humidity recorded up to 3 months Reports of the data are available to download onto an csv spreadsheet The records may be displayed 10 25 50 or 100 per page Search by date and time using the same format from timedate column ...

Страница 36: ...s the list of fans connected to the EMS and it s RPM output recorded for up to 3 months Reports of the data are available to download onto a csv spreadsheet The records may be displayed 10 25 50 or 100 per page Search by date and time using the same format from timedate column ...

Страница 37: ...our time zone and restart the EMSfor the setting to change SMTP Settings This must be set to allow emails alerts alarms to be sent Server address IP Domain Add the IP or Domain of your email server Username Add the email address which will the alarms from Password Add the password of the email address Make sure that the default admin email address is changed to the administrator who is going to be...

Страница 38: ...he bottom of the table then fill the fields with the required information There are 5 levels of access R Read only user can only access DASHBOARD TAB RC Read only camera user can only access DASHBOARD Camera TAB W Write user access to all TABs other than Camera and EMS settings TAB WC Write and Camera user can access almost all TABs other than EMS Settings TAB S Super user can access all TABs Once...

Страница 39: ...SNMP client application in order to access the EMS Name The SNMP user name Two users are defined ems ro for read only access ems rw for read write access Level The security level to be used for SNMP operations This can not be changed from the pre set authentication and privacy Auth Protocol The protocol to be used when authenticating the user Select the from the list Authentication Passphrase The ...

Страница 40: ...S Permissions The level of access to be granted for the community Read only the rocommunity for read only access Read write the rwcommunity for read write access Community String The name of the community Leave blank to disable this type of access Actions Select the save icon to save the settings for the SNMP v2c community ...

Страница 41: ...t sales usystems com Product Datasheet Available at www usystems com Europe Systems House 235 Ampthill Road Bedford MK42 9QG UK Tel 44 0 1234 761 720 North America 10 Glenlake Parkway Suite 130 Atlanta Georgia 30328 USA Tel 404 334 3607 Middle East Unit 706B Al Shamsi Building Al Nahda 1 Dubai United Arab Emirates Tel 97 155 998 1198 India 207 2nd Floor Regus Supreme Jayanagar 44 1 16th Cross Jaya...

Страница 42: ...tems com Product Datasheet Available at www usystems com Europe Systems House 235 Ampthill Road Bedford MK42 9QG UK Tel 44 0 1234 761 720 June 2021 Iss1 2 North America 10 Glenlake Parkway Suite 130 Atlanta Georgia 30328 USA Tel 404 334 3607 Middle East Unit 706B Al Shamsi Building Al Nahda 1 Dubai United Arab Emirates Tel 97 155 998 1198 India 207 2nd Floor Regus Supreme Jayanagar 44 1 16th Cross...