background image

The crimped end of the chimney con-
nector fits inside the furnace flue collar.
Install additional chimney connector and
elbow with the CRIMPED END TOWARD
THE FURNACE. This will allow any con-
densation in the flue to run back into the
furnace. Use 6" dia. (minimum 24 gauge)
black chimney connector.
Slope any horizontal pipe upward toward
the chimney at least 1/4 inch for each foot
of horizontal run.
You must have at least 18 inches of
clearance between any horizontal piping
and the ceiling. (See Fig. 3)
The chimney connector must not extend
into the chimney flue (See Fig. 6).
Seal each chimney connector pipe joint
with furnace cement. Also seal the pipe
at the chimney.
Use 3 sheet metal screws at each chim-
ney pipe joint to make the piping rigid.
The chimney connector may include a
section for a barometric draft regulator
between the furnace and the chimney
(Fig. 4, 5, 6, & 7). The barometric draft
regulator must be installed in the same
room (same pressure zone) as the fur-
nace.
Install the barometric draft regulator
strictly in accordance with the instruc-
tions that are provided with the baromet-
ric draft regulator.
A solid damper can be placed between
the barometric draft regulator and the
chimney. (Fig. 4, 5, 6, & 7)

1.

2.

3.

4.

5.

6.

7.

8.

9.

Drill a hole in the chimney connector
within 18" of the flue collar below the
barometric draft regulator just large
enough for the tube of the manometer.
Build a fire after all chimney connec-
tions have been made.
Use a manometer to measure the draft
in the flue. (U.S. Stove Model DG-26)
Adjust the barometric draft regulator to
obtain a draft of 0.05" - 0.06" W.C.
under stable conditions.

1.

2.

3.

4.

Rules for Connector
Pipe Installation

Adjusting the
Barometric Draft Regulator

6" SOLID DAMPER

6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)

MEASURE FLUE
DRAFT HERE

NON-COMBUSTIBLE
INSTALLATION PER
NFPA 211

RIGHT

WRONG

WRONG

  FIG. 6

                                                                                                                 FIG. 7

9

Содержание Clayton 1537Q

Страница 1: ... U WARNOCKHERSEY R FOR PARALLEL INSTALLATION WITH AN EXISTING FORCED AIR GAS OR OIL FIRED FURNACE U S ONLY FOR INSTALLATION AS A CENTRAL FURNACE DO NOT USE THIS FURNACE IN A MOBILE HOME OR TRAILER Improper Installation May Void Your Warranty Save This Manual For Future Reference CAUTION Read All Instructions Carefully Before Starting the Installation or Operating the Furnace 851239B 10 98 TM ...

Страница 2: ...e Page 5 First Paragraph tools and materials needed MATERIALS TOOLS Pencil 6 Foot Folding Rule or Tape Tin Snips Drill Hand or Electric Drill Bit For Sheet Metal Screws 1 8 Dia Screw Driver Blade Type Gloves Sabre Saw 5 16 Nut Driver or 5 16 Socket with Rachet 6 Pipe 6 Elbow Collar and Thimble as required 24 gauge min 1 2 Sheet Metal Screws 6 Inside Diameter Listed Residential Type or Building Hea...

Страница 3: ...om CAUTION HOT SURFACES Keep children away Do not touch during operation CAUTION INSPECT FLUE PIPES FLUE PIPE JOINTS AND FLUE PIPE SEALS REGULARLY TO EN SURETHATSMOKEANDFLUE GASES ARE NOT DRAWN INTO AND CIRCULATED BY THE AIR CIRCULATION SYS TEM CAUTION CLEANOUT OF THE HEAT EX CHANGER FLUE PIPE CHIMNEY AND DRAFT INDUCER IF USED IS ESPE CIALLY IMPORTANT AT THE END OF THE HEATING SEASON TO MINIMIZE C...

Страница 4: ...tional Fire Protection Association NFPA publication Chimney s Fireplaces and Solid Fuel Burning Appliances NFPA 211 The address of the NFPA is Batterymarch Park Quincy MA 02269 Keep the ashpit section free of excess ashes Do not allow ashes to stack higher than the sides of the ash pan DISPOSAL OF ASHES Place ashes in a metal container with a tight fitting lid Keep the closed container on a noncom...

Страница 5: ...PARALLEL INSTALLATION The design is such that when the blower comes on the blower on the central system also comes on The blower will only come on when the tempera ture in the plenum has reached the setting on the blower control This is to insure that there is sufficient warm air in the system to make it efficient for the unit to operate When the central system thermostat calls for heat the centra...

Страница 6: ...24 1 16 40 11 16 32 1 4 3 1 2 9 33 7 8 43 7 8 Model 1537Q Dimensions FIG 1 6 ...

Страница 7: ...ances Unit to sidewall 12 305 mm Unit to backwall 30 760 mm Chimney connector pipe to sidewall 21 530 mm Chimney connector pipe to backwall 18 460 mm Hot air ducts to combustibles 6 150 mm NOTE Install only on a noncom bustible floor REFER TO FIG 2 3 Place the furnace on a noncombus tible floor Check figures 2 and 3 Be sure you have the clearances shown from the furnace and the connector pipe to c...

Страница 8: ... APPLIANCE The chimney used for a furnace must not be used to ventilate the cellar or basement If there is a cleanout opening at the base of the chimney close it tightly LISTED FACTORY BUILT CHIMNEY Carefully follow chimney manufacturer s instructions Use only a Listed Residential Type or Building Heating Appliance Chimney If your chimney starts at the ceiling Fig 5 you will need enough 6 pipe to ...

Страница 9: ...he furnace and the chimney Fig 4 5 6 7 The barometric draft regulator must be installed in the same room same pressure zone as the fur nace Install the barometric draft regulator strictly in accordance with the instruc tions that are provided with the baromet ric draft regulator A solid damper can be placed between the barometric draft regulator and the chimney Fig 4 5 6 7 1 2 3 4 5 6 7 8 9 Drill ...

Страница 10: ...t on rear of furnace cabinet as shown in Figure 11 Remove blowers from cartons Remove junction box cover At tach clip nuts as per Figure 11 Install blowers and gaskets with 1 4 20 x 3 4 bolts as shown Wire right side blower first per wiring diagram Figure 12 and replace cover on junction box on blower Wire left blower same as above and replace cover Completeallwiringinjunctionbox by referral to th...

Страница 11: ...11 Honeywell FAN LIMIT CONTROL 4 ELECTRICAL JUNCTION BOX BLOWER ASSEMBLY GASKET CLIP NUTS DO NOT USE CLIP NUT ON UPPER CENTER HOLE Blower Component Assembly FIG 11 ...

Страница 12: ... B L A C K BLACK RED 110 VAC 60 HZ WHITE BLACK FORCED DRAFT BLOWER BLUE BLACK WHITE WHITE BLACK BLOWER BLOWER BLACK WHITE FAN CONTROL CENTER FRONT BLUE BLACK BLACK 1 2 3 4 5 6 COIL COIL BROWN BLUE BLACK R G C W Y FAN CONTROL CENTER FRONT ROOM THERMOSTAT 24 VOLT NOTE WHEN USING A ROOM THERMOSTAT YOU MUST BREAK OFF JUMPER FOR LOW VOLTAGE ...

Страница 13: ...ge pipe and elbows to be purchased separately maintaining the proper clearancesforthespecificmodel Makesurethat the proper clearances as stated on the label and earlier in this manual are maintained Seal the smoke pipe in the chimney with furnace cement The chimney connector shall be securely sup ported and joints fastened with sheet metal screws or rivets e Install 8 diameter heat pipe to plenum ...

Страница 14: ...power Remove filter if provided Do not expect to keep home at normal temperatures Do not load fuel above bottom of feed door Set ash pan spin draft maximum one turn open 1 2 3 4 2 MIN AIR SPACE REQUIRED BY CODE 18 MIN CENTRAL FURNACE U S ONLY FIG 13 14 ...

Страница 15: ...COLD AIR DUCT 6 PIPE DAMPER OPTIONAL 11 RPT 90 ELBOW FURNACE PIPE CONNECTOR Central Installation U S Canada FIG 14 15 ...

Страница 16: ...COLD AIR DUCT 6 PIPE DAMPER 90 ELBOW FURNACE PIPE CONNECTOR EXISTING GAS OIL ELECTRIC FURNACE 8 PIPE Add On Installation U S Only FIG 14 1 16 ...

Страница 17: ...CTRIC TRANSFORMER AND COMBUSTION FAN OF SOLID FUEL UNIT H N POWER SUPPLY FURNACE BLOWER MOTOR FAN LIMIT COMBINATION CONTROL GAS OIL ELECTRIC POWER SUPPLY JUNCTION BOX JUMPER IN CAUTION DO NOT CONNECT PLENUM FAN CONTROL SWITCH ACROSS FURNACE LIMIT CONTROL 17 ...

Страница 18: ...become shorter change color and produce less smoke Once the fire is WELL ESTABLISHED add coal to the center of the firebox forming the cone Burning in this fashion allows heat to drive off the volatile gases and turbulence created increases the burn efficiency There will have to besomeexperimentingwiththeindividualsetupasnotwochimney sorinstallationsaregoingtobethesame Just remember to allow enoug...

Страница 19: ...spin damper or thermostat open for a few minutes until the volatile gases have burned off It is not necessary to shake down the ashes each time you refuel the furnace Experience will be your best teacher BANKING THE FIRE For extended operation such as overnight the fire will need to be banked To do so heap coal up along the sides and back of the firebox so that the fire gradually burns it over a l...

Страница 20: ...osote The creosote vapors condense in the rela tively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes an extremely hot fire When coal is burned the products of combustion combine with moisture to form a soot residue which accumulates on the flue lining When ignited this soot makes an extremely hot fire The chimne...

Страница 21: ...43A Forced Draft Blower 1 3 80129 Wall Thermostat 1 4 83250 Kep Nut 1 4 20 4 5 83339 Hex Bolt 1 4 20 x 3 4 BL OX 4 6 68618 Blower Mounting Plate 1 7 68231 Fan Control Cord Assembly 2 N S 80006 Wire Nut 73B 4 21 11DIK DRAFT INDUCED KIT N S NOT SHOWN 1 2 3 4 5 6 7 7 ...

Страница 22: ...Model 1537Q Parts 22 ...

Страница 23: ...inet Top Assembly 1 17 23459 Cabinet Back 1 18 22761 Flue Collar Ring 1 19 80230 Blower Motor 2 20 24179 Feed Door Handle 1 21 89574 Coil Door Handle Brass Plated 2 22 83444 Locknut 1 2 13 2 23 83446 Flatwasher 9 16 ID 1 24 23786 Door Latch 1 N S 83409 Bolt 1 4 x 1 2 Hex 2 N S 80372 Nut 1 4 Hex 2 N S 23787 Smoke Door Clip 2 N S 83445 Bolt 1 4 20 x 1 1 4 2 N S 83250 Nut 1 4 20 Kep 2 25 80145 Limit ...

Страница 24: ...COLD AIR RETURN FILTER BOX SOLID FUEL FURNACE EXISTING FURNACE WARM AIR TO EXISTING DUCT WORK INSTALLATION A APPENDIX 24 ...

Страница 25: ...COLD AIR RETURN FILTER BOX SOLID FUEL FURNACE EXISTING FURNACE WARM AIR TO EXISTING DUCT WORK INSTALLATION B PLENUM COLLECTOR BOX 25 ...

Страница 26: ...COLD AIR RETURN FILTER BOX SOLID FUEL FURNACE EXISTING FURNACE WARM AIR TO EXISTING DUCT WORK INSTALLATION C PLENUM ELBOW PLENUM TOP OPTIONAL 26 ...

Страница 27: ...ONTROL LOCATION FURNACE PLENUM EXISTING FURNACE ANTI BACKDRAFT FLAPPER SOLID FUEL FURNACE COLD AIR RETURN INSTALLATION D 2 MINIMUM CLEARANCE DUCT WORK FURNACE PLENUM EXISTING FURNACE SOLID FUEL FURNACE COLD AIR RETURN INSTALLATION E BAFFLE U S ONLY U S ONLY 27 ...

Страница 28: ...E DUCT WORK FURNACE PLENUM EXISTING FURNACE SOLID FUEL FURNACE COLD AIR RETURN INSTALLATION F 2 MINIMUM CLEARANCE DUCT WORK SOLID FUEL FURNACE INSTALLATION G COLD AIR RETURN TO FILTER BOX CENTRAL FURNACE INSTALLATION 28 ...

Страница 29: ...2 MINIMUM CLEARANCE EXISTING OIL ELECTRIC OR GAS FURNACE SOLID FUEL FURNACE INSTALLATION H EXISTING OIL ELECTRIC OR GAS FURNACE SOLID FUEL FURNACE TOP VIEW FRONT VIEW 29 ...

Страница 30: ...easoned or dry b Thermostat setting too low for type fuel a Insufficient draft b Smothering fire when adding fresh fuel a Set thermostat higher b Clean chimney c Add raincap to chimney a Allow wood to season in a dry well ventilated area for six months b Set blower control to higher temperature See Page 18 c Set flue draft See Page 9 a Wire unit properly b Replace blower control c Replace relay d ...

Страница 31: ...31 Notes ...

Страница 32: ...BER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING IN FORMATION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESCRIPTION 3 THE MODEL NUMBER 1537Q 4 THE SERIAL NUMBER ____________________ UNITED STATES STOVE COMPANY 227 INDUSTRIAL PARK ROAD P O BOX 151 SOUTH PITTSBURG TN 37380 423 837 2100 COMPANY U NITED STATES STOV E C S S U WARNOCKHERS...

Отзывы: