For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park
Models
3. Modular Homes & Buildings
SEALED COMBUSTION
DOWNFLOW GAS FURNACES
Forced Draft with Direct Ignition (Hot Surface)
FURNACE SET---UP CHECK LIST
IMPORTANT: ONLY INDIVIDUALS HAVING PROVEN EXPERIENCE WITH THIS TYPE OF EQUIPMENT
SHOULD ATTEMPT TO PERFORM SET--UP.
-
HAS ROOF JACK CROWN BEEN CORRECTLY
INSTALLED?
-
HAS FURNACE GAS VALVE AND BURNER ORI-
FICE BEEN CORRECTLY CONVERTED FOR L.P.
GAS WHERE APPLICABLE?
-
HAS FURNACE GAS VALVE BEEN DE---RATED
FOR ALTITUDES ABOVE 2000 FEET WHERE
APPLICABLE?
-
IS GAS LINE OUTLET PRESSURE PROPERLY
SET FOR FUEL TYPE?
(NATURAL GAS IS 3.5”
W.C.; L.P. IS 10” W.C.)
-
IS PRIMARY AIR PROPERLY ADJUSTED PER
INSTALLATION INSTRUCTIONS?
-
IS CROSS---OVER DUCT INSTALLED PER
HOME BUILDER AND EVCON INSTALLATION
INSTRUCTIONS?
-
HAS FURNACE BEEN OPERATED THROUGH A
COMPLETE HEATING CYCLE?
IMPORTANT: PROPER FURNACE SET--UP AND ADJUSTMENT IS THE RESPONSIBILITY OF THE
RETAILER/HOMEOWNER AND IS NOT COVERED UNDER WARRANTY.