To enter in the settings, maintain the button SET 5 seconds. A «1» appears. Scroll with UP or DOWN until the
wanted function, then SET to enter in this function. Then, modify the value with UP or DOWN (Be carefull, if no
button is pressed for 5 seconds, the display goes out of the automatic settings mode).
D6
Programmable function settings
LED
viewer
Definition
Function
Value
Description
1
Options of Gate
opening direction
1-1
Clockwise opening The function can adjust the direction
of gate opening. The factory setting
is « 1-1 ».
Counterclockwise
opening
1-2
2
Automatic closing
2-0
No automatic
closing
This function allows to adjust the
gate closing automatic after the
paused time.
The factory setting is « 2-0 » : no
automatic closing
Un appui simultané sur les
deux touches du haut de la
télécommande (portail ouvert
ou fermé) désactivera le mode
automatique(confirmation avec 3
clignotements du feu clignotant).
Refaire l’opération pour réactiver
le mode automatique (confirmation
avec 3 clignotements du feu
clignotant).
2-1
5 seconds
2-2
15 seconds
2-3
30 seconds
2-4
45 seconds
2-5
60 seconds
2-6
80 seconds
2-7
120 seconds
2-8
180 seconds
3
There actions of
photocell/ safety
edge/ loop de-
tector when they
detecting
3-1
See below
Please do the function setting after
H&J
The factory setting is « 3-1 »
3-2
3-3
3-1 : Input PH1 active only at closing (total reopening in case of passage during the closing)
Input PH2 active only at opening (total reclosing in case of passage during the opening)
3-2 : Input PH1 active only at closing (total reopening in case of passage during the closing)
Input PH2 active at opening and closing (direction changing during 2 seconds if the gate is moving)
3-3 : Input PH1 active only at closing (total reopening in case of passage during the closing)
Input PH2 active only at closing (total reopening in case of passage during the closing).
Closed and stopped gate, a passage triggers the opening (total)