2VOICE SIDE WIRING INSTRUCTIONS
TC
gateway
2voice
power unit
TC
secondary
calling station
secondary
calling station
C1
C2
D
apartment station
column
A1
Bv1
1
2
Bv2
A2
to the Ipercom
system
Cx = distance between gateway and calling station
D = distance between gateway and 2Voice power unit
Ax = distance between 4-user distributor and apartment station
Bvx = distance between gateway from where the backbone derives and the most distant 4-user distributor
MAXIMUM DISTANCES
Wire
Number of
apartment
stations
Distance
Extension
(*)
Cx
D
Ax
Bvx
Ax+Bvx
2Voice wire Ref. 1083/92
128
200m
5m
50m
200m
200m
800m
2Voice wire Ref. 1083/94
100
125m
5m
50m
125m
125m
800m
(*) The system extension is given by the sum of all its sections: C1+C2+D+Bv1+Bv2+A1+A2+…+An
For more information on wire types and respective distances follow the rules shown in the 2VOICE SYSTEM
manual, section 2.
WIRING INSTRUCTIONS IPERCOM SIDE
Ethernet RJ45 wire
The IperCom system was developed for operating with EIA/TIA 568B standard.
Connect the wire to one of the RJ45 connectors with Urmet logo.
Insert the wire in the guide respecting the color-coding shown (Standard T568B).
8
1
Wire
No.
Cable colour
1
White-Orange
2
Orange
3
White-Green
4
Blue
Wire
No.
Cable colour
5
White-Blue
6
Green
7
White-Brown
8
Brown
Grey sheath
•
•