INSTALLATION TIPS FOR FOGGING SYSTEMS
Please observe the following instructions for installing
UR Fog
:
1. The unit must be installed avoiding to obstruct escape routes.
2. Verify the fog does not limit the visibility near: stairs, landings, moving objects that may cause: falls down, injuries or any damage to
persons.
3. Do not look directly into the nozzle. Use only authorized fluids and original bags.
4. The heather box may reach high temperatures, touch it may cause burns.
5. When
UR Fog
produces fog avoid staying closer than 1 meter from the unit.
7. Report the Fog Unit installation to the firefighters in your area and eventually to other institutions if needed. Before testing the unit
remember to report it to the firefighters in your area to avoid false alarms.
8. Remember to stick on a window in a visible place the included warning label.
9. Do not move the machine when it is still hot.
10. It is necessary to add an external switch to separate the fog generator from the alarm system and it should be activated before
the maintenance to avoid that input tests, for example, can activate the fog generator.
11. Never direct the fog jet towards an object or a wall less than 2 meters away and if possible increase the suggested minimum distance.
Thanks to the power of the jet,
UR Fog
reaches and exceeds more than 10 meters away in the first 3 seconds from the point where the
machine is installed.
12. Setting the shooting time interval between the minimum and maximum shown in the shooting table, avoid “overshooting” even if the
produced fog is dry and generally doesn’t leave residue. A shot that goes far beyond the recommended seconds can create a residue
problems in the room.
13.
UR Fog
continues to be effective for up to 2 hours without 220V and 110V mains power thanks to the insulation system which
maintains the temperature in the heating system.
14. Install at an height of about 2,5 meters not to let it be reached, avoiding possible tampering.
15. The unit has a nozzle inclination of 15° oriented to the floor.
16. The main body of
UR Fog
, which has the heating system enclosed inside a metal frame, should not be opened unless by specific and
authorized service centers. Do not open and touch for any reason the insulation before 24 hours the unit has been shut off. The internal part
may reach really high temperature.
17. Do not activate the
UR Fog
machine before the installation is completed.
18. Insert the bag as last installation procedure.
19. When the installation is finished, always test the system with a trial shoot (suggested 4 seconds)
20. After connection to mains power at least one hour is necessary to reach the minimum temperature needed to generate fog.
21. Install
UR Fog
avoiding any obstacles in front of it which can prevent the spreading of the fog.
22. The external temperature of
UR Fog
can be higher from room temperature up to 50 °C.
23. Connecting to the mains the edge of a stranded conductor should not be soft-soldered
24. The
UR Fog
machine should not be exposed to water spray or dripping.
25. The content of fluid bags is meccanically pre-determined , the tollerance is in the range -10% +10%
26. Request to
UR Fog
or its distributors to take part in courses for installers to ensure the optimal installation of the equipment.
17
DEFECT FOUND POSSIBLE CAUSE POSSIBLE SOLUTION
Red front led ON
Bag changed ,reset needed
Follow instructions Paragraph 13
Unit ARMED
(BLUE LED ON)
but don’t execute trig command
Green front led is OFF
Unit still warming , wait max 120min. with the unit
connected to the mains power for 1st time
activation
Wires error
Verifify to have 12V beetween TRGP and TRGN
when alarm is ON.
Empty bag- replace it following instructions on
Paragraph 13
Mains power overload
Try a complete power down (mains and battery)
to recover unit. With no results board needs to
be replaced
Electronic Board overheath
Clean side air flow holes
Unit cannot be ARMED
BLU LED OFF
Wires error
Verifify to have 12V beetween ARMP and ARMN
when alarm panel is active.