Do not obstruct the nozzle when the generator is armed and bag is in.

The value in the first column indicates the volume of the room to be protected, with respective seconds of emission reported in the 
second column. The value in m³ varies depending on the density to be obtained. With the suggested value it is possible to get the ma-
ximum density recommended to ensure the absence of any residual. In places where a little residual causes no problems, it is possible 
to increase the shooting time. Please note that the more fog released, the more the time required to recover visibility. High levels of fog, 
over recommended limits, can leave residual. Any residue usually goes away by itself within 24/48 hours, otherwise, being soluble in 
water, it is enough to use a wet cloth for cleaning. If you desire to obtain an average of 1 meter visibility after 60 seconds, as specified 
by the standard EN 50131-8 : 2019, as used as reference by all manufacturers of Fog generators, the number of shooting seconds it 
is to be reduced in half.

SHOOTING TABLE MODULAR 4 PLUS (max 46 sec.)

SHOOTING TABLE MODULAR 5 PLUS (max 48 sec.)

SHOOTING TABLE MODULAR 8 PLUS (max 69 sec.)

   m³ to protect

         

Seconds of emission   

     

m³ to protect     

      

Seconds of emission

     

    m³ to protect       

  

Seconds of emission

         50 (150*)                      6                            150 (450*)                     21                         300 (900*) 

            40

         75 (225*)                      9 

                   200 (600*)                     23                         400 (1200*)                     46

        100 (300*)                    12                           250 (750*)                     35 

   m³ to protect

         

Seconds of emission   

     

m³ to protect     

      

Seconds of emission

     

    m³ to protect       

  

Seconds of emission

         50 (150*)                      6                            150 (450*)                     16                         300 (900*) 

            27

         75 (225*)                      9 

                   200 (600)                     21                         400 (1200*)                     37

        100 (300*)                    12                           250 (750*)                     24                         500 (1500*)                     48 

   m³ to protect

         

Seconds of emission   

     

m³ to protect     

      

Seconds of emission

     

    m³ to protect       

  

Seconds of emission

         50 (150*)                       5                            200 (600*)                    19                       500 (1500*)                      43                                                                      
         75 (225*)    

         8 

                    250 (750*)                    22                        600 (1800*)                       51

        100 (300*)                     10                           300 (900*)                    26                        700 (2100*)                      60
        150 (450*) 

        14                          400 (1200*)                   35                        800 (2400*)                      69

*

Industrial standard as from other manufacturers

SHOOTING TABLE MODULAR 2 PLUS (max 28 sec.)

   m³ to protect

         

Seconds of emission   

     

m³ to protect     

      

Seconds of emission

     

    m³ to protect       

  

Seconds of emission

         50 (150*)  

         7                            100 (300*)                    14                           200 (600*) 

            28

         75 (225*)    

         9 

                    150 (450*)                     21           

 

SHOOTING TABLE MODULAR 3 PLUS (max 40 sec.)

   m³ to protect

         

Seconds of emission   

     

m³ to protect     

      

Seconds of emission

     

    m³ to protect       

  

Seconds of emission

         50 (150*)                       7                            150 (450*)                    21                           300 (900*) 

            40

         75 (225*)    

         9 

                    200 (600*)                    28

        100 (300*)                     14                           250 (750*)                    35

                    RECOMMENDED SHOOTING SECONDS ACCORDING TO THE VOLUME SPACE TO PROTECT (m

3

)

Fogging systems Modular CPlus are able to produce fog continuously till the maximum time allowed , according to the model 
specifications. There might be cases in which, due to specific characteristic of the location, levels of air temperature and pressure, 
degree of the fog density and light in the target area, that the shooting time can be increased or decreased. For example, above 
5 m of height the shooting time must be 20% more and above 7 m , every additional meter should be consideredas double.

                                                                                   

                                                                              
                                                                                  (HxLxP) x D x V x R x I

HxLxP--------Height x Width x Depth of the area to protect
D-------------Density of the produced fog
V-------------Temperature and air pressure
R-------------Acceptable residue in case of saturation of V parameter
I--------------Intensity of the surface light

The following tables indicate the suggested fog emission in relation to the number of seconds of shooting set in average condition of 
temperature, air pressure and humidity.

                         SHOOTING TIME SETTING

To set the shooting time, after removing the plastic front cover , in the middle of PCB is located the FIRETIME (S2) button.Holding down 

the button , the 3 coloured front leds will flash and a sound is signal is executed by the buzzer , each flash/beep is equivalent to one 

second of fog emission of the device.

Pressing the button again, the shooting time is not added to the one previously set, but will restart from zero.

If the button is pressed for a time higher of the unit capabilities , the fog emission will be set to the maximum allowed for the unit.

N.B. Before opening the cover ensure that the control panel is set to “service”, so that the opening of “anti-sabotage or 

tamper” circuit does not cause any shooting.

N.B. Shooting time can be set according to whished seconds, but to correclty activate the bag reserve in full security, it 

must be set to a minimun 4 seconds of shooting.

N.B. 

To correctly dimension the machines it is needed to verify that the saturation of the area occurs in faster time than the one 

        supposed for the theft.

Содержание Plus Series

Страница 1: ......

Страница 2: ...e automatically accepted by breaking the security labels on the product 1 PACKAGE CONTENT Inside the package you will find 1 The Unit Modular CPlus 2 One 750 ml bag Optional 1000 ml 3 A window label to indicate the device installation 4 Installation and use manual 2 19 WARNING All UR FOG fogging systems should only be used with UR FOG branded flu ids It is strictly forbidden to use any fluid not p...

Страница 3: ...eason you swallow fog fluid or if after contact with eyes or skin you have any kind of reaction and in any case wash it immediately with water and soap Do never stay for a long time in a room filled with fog Do not use charged bags that are not the ones suggested by UR Fog and never try to recharge them they are made for a single use Follow your national rules for the dispose of empty bags Keep UR...

Страница 4: ... 5 meters not to let it be reached avoiding possible tampering 15 The unit has a nozzle inclination of 15 oriented to the floor 16 The main body of UR Fog which has the heating system enclosed inside a metal frame should not be opened unless by specific and authorized service centers Do not open and touch for any reason the insulation before 24 hours the unit has been shut off The internal part ma...

Страница 5: ... minutes 140 minutes 150 minutes 37 41 W 42 47 W 42 47 W 48 53 W 1 4 A 1 7 A 1 9 A 2 1 A microswitch microswitch microswitch microswitch Yes Yes Yes Yes LAN WIFI board support Yes Yes Yes Yes Yes 16 14 DEFECTS POSSIBLE SOLUTION DEFECT FOUND POSSIBLE CAUSE POSSIBLE SOLUTION Disturbance interference or potential differences between devices In the evenience of high noise on mains power lightings an e...

Страница 6: ...to the following parts by skilled operators 1 Verify battery and power supply status 2 Verify screws are firmly closed 3 Verify the output nozzle is not damaged and without anyting inside 4 Verify pneumatic circuit 5 Verify once a year liquid pump BATTERY AND POWER SUPPLY CHECK Verify that the output of the power supply without any load battery unplugged is 14 1 V on the PSU and 13 8 V on FASTON b...

Страница 7: ...a qualified technician Connect the equipment to the electricity grid only after you have completed the installation It is necessary to connect the ground terminal The system must be connected to the mains trough on automatic switch automatic switch curie C with Ih 10 A and Idif 30 mA with breching capacity based on the assumed fault current of the fogging system in the sampling point PLEASE NOTE T...

Страница 8: ... and will work in parallel with the commands received by the serial interface In no case a voltage greater than the board s power supply should be applied to any pin of this port except for relay outputs that can manage up to 60V 500mA Some interface options depend on S3 Dip Switch configuration and W1 and W2 jumpers Fig 2 shows their position on the board FUNCTION DIP SWITCH fig 1 Tab 1 13 11 INS...

Страница 9: ...stem is activated by an event detected by an area or sensor Please note that is ARM costant signal is removed during the shooting the units immediatly stops fog emission Optional shooting methods There are also some other activation methods on Modular Plus series some of them depending also from other optional devices that let the installer able to satisfy the most common customer s requests A Add...

Страница 10: ...E MODULAR 3 PLUS max 40 sec m to protect Seconds of emission m to protect Seconds of emission m to protect Seconds of emission 50 150 7 150 450 21 300 900 40 75 225 9 200 600 28 100 300 14 250 750 35 RECOMMENDED SHOOTING SECONDS ACCORDING TO THE VOLUME SPACE TO PROTECT m3 Fogging systems Modular CPlus are able to produce fog continuously till the maximum time allowed according to the model specifi...

Отзывы: