Uponor Climate Co˘ntrol™ Zoning System Installation Guide
21
Connections
Warning:
Disconnect the power before
installing or changing the device wiring.
Additional Base Units
• For an installation with more than one manifold or
more than 12 channels, install additional base units
(up to three).
• A single interface drives all three base units.
• Each base unit must be fitted with an antenna.
Connections Between Base Units
STOP
The connections between the base units
are polarized.
• Base unit #1 is the controller connected to
the interface.
• Connect terminal 5 and 6 of base unit #2 to terminal
5 and 6 of base unit #1.
• Connect terminal 7 and 8 of base unit #3 to terminal
7 and 8 of base unit #1 or base unit #2.
Circulation Pump Relay
If separate pumps are used for each manifold, each pump
relay can be connected to its own base unit.
See:
Section 3: Base Unit Installation.
For a System with Several Base Units
Attention:
If a common pump supports
multiple manifolds, a pump relay can be
connected to the closest base unit. See the
circulation pump supplier documentation
before performing the connection.
Pump Relay
Pump
Pump Relay
Pump
Pump Relay
Pump
Power Supply
Power Supply
Power Supply
Common Pump
Individual Pumps