![Uplink 202132UP455013 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/uplink/202132up455013/202132up455013_installation-and-user-manual_1060808033.webp)
32
4G CELLULAR
ALARM COMMUNICATOR
INSTALLATION (cont.)
I. Completing the Installation and Testing
Once the physical installation is completed, the unit is activated from the Dealer
Web Site, and programming changes are made, test the 4550-CF along with the
alarm panel to ensure everything is functioning properly.
Test the following:
a. Check to see that all 5 LEDs are green. The first 4 LEDs should be solid
green, and the 5th LED should be flashing green.
b. Disconnect the Telco Line, wait the appropriate period of time, then check
to see that 1) the Telco LED has turned solid red, and 2) a Telco Trouble
condition has been reported to the monitoring central station (if this feature
is active).
c. With the Telco Line still disconnected, trip an alarm on the alarm panel.
Check that the 4550-CF has correctly intercepted the panel’s digital dialer
output and reported the event to the central monitoring station. Reconnect
the Telco Line.
d. If using one or both of the inputs on the 4550-CF, check to ensure both are
properly activated and report to the central station.
e. If using one or more of the Output Relays on the 4550-CF, then go back
to the Dealer Web Site and use the Switch Output Relay command to test
each relay. Make sure the alarm panel properly detects the relay’s change
of state and reports the proper event to the central station.
f. Remove AC power and Battery Power from the 4550-CF, then trip an alarm
on the alarm panel. Confirm the panel’s digital dialer properly sends this
event to the central station. Reconnect AC and Battery.