29
®
4550-CF
INSTALLATION (cont.)
G. Programming and Central Station Reporting
Programming requires the telephone number of the monitoring central station’s
alarm receiver and/or its IP address and Port number. Determine whether to use
the default settings for the events to be reported or customize them by completing
the following:
Use this web site to program:
a. Which alarms will be sent to the central station via a telephone dialer.
b. The telephone number of the central station receiver where all of the
signals should be sent.
c. The account number to be sent to the central station for events generated
by the 4550-CF.
d. What event codes should be sent for the 2 Inputs/zones (for both the
normal and alarm states).
e. What event codes should be sent for Low Battery and Low Battery
Restoral.
f. Whether alarm events should also be sent to an email account, and the
email account’s address.
The following parameters can be configured from the Dealer Web Site;
1. Dialer Intercept Mode Status
(Default=Intercept determined by Line Monitor).
The 4550-CF normally uses its built-in Telephone Line Monitoring circuit to
determine whether the unit should intercept the alarm panel’s digital dialer
or leave it connected to the premises telephone line. However, the unit can
be programmed from the Dealer Web Site to permanently intercept the
panel’s dialer (RF Only Mode) or never intercept the panel’s dialer.
2. Automated and On Demand Test Signals
(Default = Weekly)
The Automated Test signal interval can be changed to Daily or Weekly
from the Dealer Web Site. In addition, an immediate test signal can be
generated.
(INSTALLATION continued next page)