crooked on bracket, bracket not bent or loose on main 
burner).

8.

Adjust the manifold pressure to the required IWG with 
gas supplied to the unit at a pressure of 7 to 10.5 inches 
WC. 

9.

If burning at the orifices, excessive yellow tipping, or 
excessive noise is observed during any phase of main 
burner operation, adjust the main burner air shutters 
(See Figure 1) to eliminate the problem(s).

10. With main burners ignited, check for gas leaks, espe-

cially in the following locations: pilot tubing connection at 
the pilot, pilot tubing connection at the gas valve, gas 
valve inlet and outlet connections, manifold union in the 
burner compartment, and main burner orifices where 
they thread into the manifold. Repair any leaks found, 
and recheck. DO NOT CHECK WITH OPEN FLAME.

11. With main burners off, disconnect the manometer and 

replace the manifold plug. Check for gas leaks at this 
plug.

12. Remove jumpers and replace all access panels.

Manifold pressure for the respective BTU/HR input or out-
put must be adjusted to the IWG as specified on the ori-
fice label (035-07981) located on the inside of the unit gas 
heat access panel.

 FIGURE 1 - MAIN BURNER, PILOT TUBE, GAS 

MANIFOLD AND ADJUSTABLE SHUTTERS

PARTS SUPPLIED WITH THIS ACCESSORY

ITEM

QTY.

PART NO.

DESCRIPTION

1

8

9584

Burner Orifice, #31

2

2

9570

Pilot Orifice, #60

3

2

9571

Pilot Orifice, #61

4

2

9574

Pilot Orifice, #66

5

1

10433

High Altitude Conversion Label (to 
4,500 ft.)

6

1

10434

High Altitude Conversion Label (to 
6,000 ft.)

7

1

10561

Conversion/Modification Label

8

1

10757

Accessory Instruction Form 

Содержание 1HA0409

Страница 1: ...aving jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified agency performing this work assumes responsibility for the proper conversion of this appliance with this kit For U S units installation must comply with the National Fuel Gas Code ANSI ...

Страница 2: ...as were disconnected in Step 2 and 3 or refer to the unit wiring diagram 14 Mark the appropriate data burner orifice size manifold pressure and heat exchanger input capacity on the conversion labels provided and install them adjacent to the unit data plate 15 Refer to the Gas Heat section of the unit installation instructions for proper installation and start up proce dures TESTS AND ADJUSTMENTS A...

Страница 3: ...er orifices where they thread into the manifold Repair any leaks found and recheck DO NOT CHECK WITH OPEN FLAME 11 With main burners off disconnect the manometer and replace the manifold plug Check for gas leaks at this plug 12 Remove jumpers and replace all access panels Manifold pressure for the respective BTU HR input or out put must be adjusted to the IWG as specified on the ori fice label 035...

Страница 4: ...ge without notice Printed in U S A 10757 UAI B 1204 Copyright by Unitary Products Group 2004 All rights reserved Supersedes 10757 UAI A 0602 035 13073 001 A 0602 Unitary 5005 Norman Products York OK Group Drive 73069 ...

Отзывы: