3 Electrical installation
Q3 1000-2000A
15
Attention:
The order of the connections to the connector numbers or screw terminals is obli-
gatory. All further advice is non-obligatory.
The input and output conductors may be altered or supplemented in accordance
with the electrical standards.
Note:
- Connection and operating instructions
- Local regulations
- EU guideline 89/392/EWG
- VDE and TÜV regulations and Trade body guidelines
Switch on
the auxiliary voltage and the supply voltage simultaneously.
Switch off
the supply voltage after the auxiliary voltage
Input filter
see CE advice, page 14
Short conductor length to be used between the input filter and the device
Auxiliary voltage connection
Connection
terminal X5:17, X5:18
Power supply
400V~ ±15%
Special voltages
24V~, 110V~, 230V~, 500V~
Input current
max. 300mA
Phase position
regardless
Internal fuses
FE1, FE2 0.8AT
- Min. line cross-section 0.5mm²
- External fuse
- Min. line protection 6A
Note:
Observe the respective type plate.
Control voltage XXX
P
o
w
er
co
nn
e
ct
io
n
Содержание Classic Q3 400 Series
Страница 10: ...Classsic Q3 1000 2000A 10 Dimensions ...
Страница 11: ...3 Electrical installation Q3 1000 2000A 11 Dimensions ...
Страница 13: ...3 Electrical installation Q3 1000 2000A 13 Connections ...
Страница 18: ...Q3 1000 2000A 18 Free ...
Страница 20: ...Q3 1000 2000A 20 Field regulator is not installed External field current regulator F2 1 xx Field connection ...
Страница 23: ...5 Adjustments Q3 1000 2000A 23 Circuit diagram ...